PowerFlex 20-HIM-A6 and 20-HIM-C6S HIM
(Human Interface Module)
Firmware Revisions FRN 1.xxx - 2.xxx
User Manual
Original Instructions
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are
required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may
be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from
the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
Labels may also be on or inside the equipment to provide specific precautions.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous
environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 3
Summary of Changes
This manual contains new and updated information as indicated in the following
table.
Topic Page
Added the PowerFlex® 755T drives to the product compatibility list. 12
Imported a diagram of the PowerFlex 755T-series drive 16
Added a note to the Process Screen section 29
Added a note to the Creating a User-Defined Drive/Peripheral Name section 37
Added a note to the Customizing the Process Screen section 38
Replaced ‘password’ with ‘access code’ (except in references to user interface elements) 50…61
Added a note to the Updating the HIM Firmware or Language section 65
Deleted Appendix C – History of Changes
4 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Summary of Changes
Notes:
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 5
Table of Contents
Preface
Conventions Used in This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Rockwell Automation Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Local Product Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Technical Product Assistance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Chapter 1
Getting Started
HIM Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Compatible Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Chapter 2
Installing the HIM
Installing the 20-HIM-A6 HIM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
In the Drive HIM Bezel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Using Drive Port 2 Connection for Hand-Held Operation . . . . . . 16
In a Remote-Mount HIM Bezel (20-HIM-B1). . . . . . . . . . . . . . . . . . 17
Installing the 20-HIM-C6S HIM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Removing the HIM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Chapter 3
HIM Components
HIM Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Soft Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Navigation and Number Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Single-function Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
LCD Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Status Bar. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Data Area. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Soft Key Labels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Main Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Status Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Process Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Control Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Folder Screens. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Fault Display Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
6 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Table of Contents
Chapter 4
Using the HIM
Initial HIM Operation on New Drive Powerup. . . . . . . . . . . . . . . . . . . . . 33
Selecting Display Contrast . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Setting the Date/Time for PowerFlex 750-Series Drives . . . . . . . . . . . . . 35
Creating a User-Defined Drive/Peripheral Name . . . . . . . . . . . . . . . . . . . 37
Customizing the Process Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Selecting Multi-Line or Single-Line View . . . . . . . . . . . . . . . . . . . . . . . 38
Changing Displayed Items, Adding a Scale Factor, or Customizing
Text . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Resetting the Drive/Peripherals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Setting Factory Defaults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Setting PowerFlex 750-Series Drives/Peripherals to Factory Defaults
40
Setting PowerFlex 7-Class Drives/Peripherals to Factory Defaults 41
Setting Display Flashing for Fault Indication . . . . . . . . . . . . . . . . . . . . . . . 42
Setting Display Flashing for Alarm Indication . . . . . . . . . . . . . . . . . . . . . . 43
Viewing/Editing Drive or Peripheral Parameters . . . . . . . . . . . . . . . . . . . . 44
Selecting File-Group-Parameter or Linear List View . . . . . . . . . . . . . 44
Direct Parameter Access Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Alternate Linear List Access Method . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Viewing/Clearing Drive Faults or Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Viewing Peripheral Diagnostic Items. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Viewing/Clearing Peripheral Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Checking Drive and Peripheral Firmware Revisions . . . . . . . . . . . . . . . . . 49
Using the CopyCat Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Creating CopyCat Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Renaming CopyCat Files. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Deleting CopyCat Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Changing PowerFlex 750-Series Drive Parameter Associations . . . . . . . 54
Using Individual Screen Entry Method. . . . . . . . . . . . . . . . . . . . . . . . . 54
Using Direct Numeric Entry Method . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Linking Parameters in PowerFlex 700/700S Drives . . . . . . . . . . . . . . . . . 57
Establishing a Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Deleting an Established Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Using an Access Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Setting/Changing the Access Code. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Changing Access Code-protected Drive/Peripheral Parameters. . . 60
Disabling Access Code Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Initiating PowerFlex 750-Series Drive Port Verification . . . . . . . . . . . . . 62
Conflict Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Resolving ‘Changed’ or ‘Requires Configuration’ Conflicts. . . . . . . 63
Resolving ‘Not Functioning’, ‘Not Supported’, or ‘Invalid Duplicate’
Conflicts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Changing Language for the Display Text . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Updating the HIM Firmware or Language . . . . . . . . . . . . . . . . . . . . . . . . . 65
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 7
Table of Contents
Appendix A
Specifications
Communications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Regulatory Compliance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Appendix B
HIM Parameters
Parameter List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Index
8 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Table of Contents
Notes:
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 9
Preface
This manual provides information about the enhanced PowerFlex® 20-HIM-A6
and 20-HIM-C6S Human Interface Modules, and using them with PowerFlex
750-Series drives and PowerFlex 7-Class drives.
Conventions Used in This
Manual
The following conventions are used throughout this manual:
Parameter names are shown in the format Parameter xx - [*]. The xx
represents the parameter number. The * represents the parameter name
for example Parameter 01 - [Port Number].
The HIM or drive firmware revision number (FRN) is displayed as FRN
X.xxx, where ‘Xis the major revision number and ‘xxx’ is the minor
revision number.
Rockwell Automation
Support
Rockwell Automation offers support services worldwide, with over 75 sales and
support offices, over 500 authorized distributors, and over 250 authorized
systems integrators located through the United States alone. In addition,
Rockwell Automation representatives are in every major country in the world.
Local Product Support
Contact your local Rockwell Automation representative for the following:
Sales and order support
Product technical training
Wa r r a n t y s u p p o r t
Support service agreements
Technical Product Assistance
For technical assistance, please review the information in Chapter 4, Using the
HIM, first. If you still have problems, then access the Allen-Bradley Technical
Support website at http://www.ab.com/support/abdrives
or contact Rockwell
Automation.
10 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Preface
Additional Resources
These documents contain additional information concerning related products
from Rockwell Automation.
You can view or download publications at http://
literature.rockwellautomation.com. To order paper copies of technical
documentation, contact your local Allen-Bradley distributor or Rockwell
Automation sales representative.
To find your local Rockwell Automation distributor or sales representative, visit
http://www.rockwellautomation.com/locations
.
For information such as firmware updates or answers to drive-related questions,
go to the Drives Service & Support website at http://www.ab.com/support/
abdrives and click the Downloads or Knowledgebase link.
Resource Description
PowerFlex 750-Series AC Drive Installation Instructions, publication 750-IN001 Information on installing and programming PowerFlex 750-Series AC drives
PowerFlex 750-Series AC Drives Programming Manual, publication 750-PM001
PowerFlex 750-Series AC Drives Technical Data, publication 750-TD001
PowerFlex 70 User Manual, publication 20A-UM001
Information on installing and programming PowerFlex 70 standard control
and enhanced control drives.
PowerFlex 70/700 Reference Manual, publication PFLEX-RM001
PowerFlex 70 Enhanced Control and 700 Vector Control Reference Manual, publication PFLEX-RM004
PowerFlex 700 Series A User Manual, publication 20B-UM001
Information on installing and programming PowerFlex 700 standard control
and vector control Series A drives, and PowerFlex 700 vector control Series B
drives.
PowerFlex 700 Series B User Manual, publication 20B-UM002
PowerFlex 70/700 Reference Manual, publication PFLEX-RM001
PowerFlex 70 Enhanced Control and 700 Vector Control Reference Manual, publication PFLEX-RM004
PowerFlex 700H Installation Instructions, publication PFLEX-IN006 Information on installing and programming PowerFlex 700H drives.
PowerFlex 700H Programming Manual, publication 20C-PM001
PowerFlex 700S with Phase I Control Installation Manual (Frames 1…6), publication 20D-IN024
Information on installing and programming PowerFlex 700S drives.
PowerFlex 700S with Phase I Control Installation Manual (Frames 9 and 10), publication PFLEX-IN006
PowerFlex 700S with Phase I Control User Manual (All Frame Sizes), publication 20D-UM001
PowerFlex 700S with Phase I Control Reference Manual, publication PFLEX-RM002
PowerFlex 700S with Phase II Control Installation Manual (Frames 1…6), publication 20D-IN024
PowerFlex 700S with Phase II Control Installation Manual (Frames 9…14), publication PFLEX-IN006
PowerFlex 700S with Phase II Control Programming Manual (All Frame Sizes), publication 20D-PM001
PowerFlex 700S with Phase II Control Reference Manual, publication PFLEX-RM003
PowerFlex 700L User Manual, publication 20L-UM001 Information on installing and programming PowerFlex 700L Liquid-Cooled
AC drives.
PowerFlex Digital DC Drive User Manual, publication 20P-UM001
Information on installing and programming PowerFlex Digital DC drives.
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 11
Chapter 1
Getting Started
The PowerFlex® 20-HIM-A6 and 20-HIM-C6S HIMs provide a communication
interface to configure and monitor PowerFlex 753 and PowerFlex 755 AC drives
and their connected peripherals. These HIMs are also backward compatible with
all PowerFlex 7-Class drives, but with limited functionality.
HIM Types
At the time of publication, the following enhanced PowerFlex 7-Class HIMs are
available.
Features
The enhanced PowerFlex 20-HIM-A6 and 20-HIM-C6S HIMs provide the
following benefits over the more basic PowerFlex 7-Class HIMs (catalog
numbers 20-HIM-A3, 20-HIM-A5, 20-HIM-C3S, and 20-HIM-C5S):
Full-numeric keypad with fully-integrated navigation capability to more
easily configure and monitor the drive and its connected peripherals.
Better keypad touch response and improved tactile feel to provide more
gratifying, error-free data entry.
More intuitive access and new menu structures that increase HIM
operating efficiency.
Simplified custom name assignments for drive/peripherals (for example,
Pump 1) to reduce required key presses.
Topic Page
HIM Types
11
Features
11
Compatible Products
12
Safety Precautions 12
HIM Catalog Number Description
20-HIM-A6
(1)
(1) Supports English, Portuguese, French, Italian, German, Spanish, and Dutch
languages. The HIM firmware can be updated in the field to support other available
languages. Important: The language selected for download at the Rockwell
Automation Web Updates website at http://www.ab.com/support/abdrives/
webupdate will replace all other supported languages—except English, which will
always remain as the default language.
NEMA Type 1 HIM
20-HIM-C6S
(1)
Remote-Mount NEMA Type 4X/12 HIM
12 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 1 Getting Started
Support for English, and customary European and Asian languages.
Dynamic soft keys that change functions/names based on screen or data
entry mode to reduce keypad keys and simplify HIM operation.
Customizable drive monitoring items that can be displayed as a list on the
process screen or as individual screens.
New flashing LCD screen to provide enhanced visibility when faults or
alarms are detected.
Compatible Products
At the time of publication, the 20-HIM-A6 and 20-HIM-C6S HIMs are
compatible with the following products:
Safety Precautions
Please read the following safety precautions carefully.
PowerFlex 753 drives
PowerFlex 755 drives
PowerFlex 755TL drives
PowerFlex 755TR drives
PowerFlex 755TM common bus inverters
PowerFlex 755TM bus supplies
PowerFlex 70 drives with standard or enhanced control
PowerFlex 700 drives with standard or vector control
PowerFlex 700H drives
PowerFlex 700S drives with Phase I or Phase II control
PowerFlex 700L drives with 700 vector control or 700S control
PowerFlex 700AFE (Active Front End)
PowerFlex Digital DC drives
PowerFlex 7000 drives
SMC™ Flex smart motor controllers
SMC-50 smart motor controllers
ATTENTION: Risk of injury or death exists from machine motion when using the
HIM to Start/Stop/Jog or configure the drive.
ATTENTION: Risk of injury or equipment damage exists. Only personnel familiar
with drive and power products and the associated machinery should plan or
implement the installation, startup, configuration, and subsequent maintenance
of the product using the HIM. Failure to comply may result in injury and/or
equipment damage.
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 13
Chapter 2
Installing the HIM
This chapter provides instructions for installing and removing the HIM.
There are two types of enhanced PowerFlex® 7-Class HIM:
NEMA Type 1 (catalog number 20-HIM-A6)
Remote-mount NEMA Type 4X/12 (catalog number 20-HIM-C6S),
which also includes a 1202-C30 interface cable for connection to the drive
Topic Page
Installing the 20-HIM-A6 HIM 14
Installing the 20-HIM-C6S HIM 18
Removing the HIM
21
20-HIM-A6 HIM 20-HIM-C6S HIM
14 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 2 Installing the HIM
Installing the 20-HIM-A6 HIM
The 20-HIM-A6 (NEMA Type 1) HIM is normally installed in the HIM bezel
(drive Port 1) on the front of the drive. For temporary hand-held operation, the
HIM can be plugged into drive Port 2 (near the bottom of the drive control pod
for PowerFlex 750-Series drives, or on the bottom of the drive for PowerFlex 7-
Class drives) using a 1 m/3.28 ft. long 20-HIM-H10 cable. For applications
requiring the HIM to be located remotely, the HIM can be installed in a remote-
mount HIM bezel (catalog number 20-HIM-B1) in a suitable location. The 20-
HIM-B1 remote-mount HIM bezel includes a 3 m/9.8 ft. long 1202-C30 cable.
In the Drive HIM Bezel
PowerFlex 750-Series IP20, NEMA/UL Open Type Drives
Place the HIM into the drive HIM bezel by inserting it straight back into the top
of the bezel and then sliding it down into the base of the bezel onto the mating
connector.
TIP
The HIM can be installed in the drive HIM bezel with the drive powered or
unpowered.
(PowerFlex 755 drive shown)
Drive HIM Bezel
20-HIM-A6 HIM
?
IN
?
DOWN
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 15
Installing the HIM Chapter 2
PowerFlex 750-Series IP54, NEMA/UL Type 12 Drives
1. Unfasten and remove the cover as shown below using the following
recommended tools:
Screwdriver: 6.4 mm (0.25 in.) flat or T20 Hexalobular
Hex socket: 7 mm
2. Place the HIM into the drive HIM bezel by inserting it straight back into
the top of the bezel and then sliding it down into the base of the bezel onto
the mating connector as shown on page 14
.
3. Replace the cover and the fasteners.
4. Tighten all screws and nuts to the recommended torque of 0.68 N•m (6.0
lb•in).
16 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 2 Installing the HIM
Using Drive Port 2 Connection for Hand-Held Operation
PowerFlex 755T-Series Drive
Attach a splitter cable to the cradle connector of the HIM. Then plug the other
end of the cable into DPI Port 02 near the bottom of the drive control pod.
PowerFlex 750-Series Drive
Attach a 20-HIM-H10 cable to the bottom of the HIM. Then plug the other end
of the cable into Port 2 near the bottom of the drive control pod.
(PowerFlex 755T
drive shown with
cover removed)
Splitter Cable
(1 m/3.28 ft. long)
20-HIM-A6 HIM
Cradle
Connector
DPI Port 02
PE
PE
20-HIM-A6 HIM
20-HIM-H10 Cable
(1 m/3.28 ft. long)
Port 2
(PowerFlex 755 drive
shown with cover
removed)
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 17
Installing the HIM Chapter 2
PowerFlex 7-Class Drive
Attach a 20-HIM-H10 cable to the bottom of the HIM. Then plug the other end
of the cable into Port 2 on the bottom of the drive.
In a Remote-Mount HIM Bezel (20-HIM-B1)
1. If the remote-mount HIM bezel is not mounted, see the HIM Bezel
Installation Instructions, publication 20HIM-IN002, for mounting
details.
2. Route the 3 m/9.8 ft. long 1202-C30 bezel cable (included with the 20-
HIM-B1 remote-mount HIM bezel) to the drive.
3. Connect the bezel cable to the DPI™ Port 2 on the drive as shown on
page 16
for a PowerFlex 750-Series drive or a PowerFlex 7-Class drive.
Port 2
(PowerFlex 70
drive shown)
20-HIM-A6 HIM
20-HIM-H10 Cable
(1 m/3.28 ft. long)
18 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 2 Installing the HIM
4. Install the HIM into the remote-mount HIM bezel.
Installing the 20-HIM-C6S
HIM
The 20-HIM-C6S (NEMA Type 4X/12) HIM is designed for remote
installation and includes a 3 m/9.8 ft. long 1202-C30 cable. See Figure 1
for
overall HIM dimensions. Choose an appropriate location to mount the 20-HIM-
C6S HIM. The distance between the HIM and drive can be increased up to 75
m/246 ft. by using a 1202-Hxx extension cable or 1202-CBL-KIT-100M cable
kit. However, a cable distance greater than 30 m/98.4 ft. is not CE compliant.
PowerFlex 755 drive shown
(without HIM in drive HIM bezel)
20-HIM-B1
Remote-Mount
HIM Bezel
3 m/9.8 ft. long 1202-C30 bezel cable included
with 20-HIM-B1 remote-mount HIM bezel.
Distances can be increased up to 75 m/246 ft.
(1)
(1) To increase this distance, use one of the following cables:
1202-H03 Extension cable (0.3 m/0.98 ft. long)
1202-H13 Extension cable (1.0 m/3.28 ft. long)
1202-H30 Extension cable (3.0 m/9.8 ft. long)
1202-CBL-KIT-100M cable
Note that a cable distance greater than 30 m/98.4 ft. is not CE compliant.
20-HIM-A6 HIM
4 b. Slide down.
4 a. Push in.
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 19
Installing the HIM Chapter 2
Figure 1 - 20-HIM-C6S HIM Dimensions
1. Drill the required hole pattern in the panel. See Figure 2 for dimensions.
TIP
A conversion template (part number 336745-C01), provided with the
20-HIM-C6S HIM, includes a drilling pattern and mounting
instructions to assist with HIM installation.
93.0
(3.66)
25.0
(0.98)
3.0 m/9.8 ft. long
1202-C30 cable
(included with
20-HIM-C6S HIM)
1202-H03 = 0.3 m/0.98 ft. long
1202-H10 = 1.0 m/3.28 ft. long
1202-H30 = 3.0 m/9.80 ft. long
180.0
(7.08)
1202-Hxx Extension Cable
(supplied separately, and only
needed if required distance
exceeds 1202-C30 Cable length)
Dimensions are in millimeters and (inches).
20 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 2 Installing the HIM
Figure 2 - Hole Pattern to Mount the 20-HIM-C6S HIM
2. Peel the protective film from the gasketed surface on the back of the HIM.
IMPORTANT
Adhesive coated gasket is designed for one-time only installation.
67.0
(2.63)
60.0
(2.36)
77.0
(3.03)
77.0
(3.03)
59
(2.32)
Ø 19.1
(0.75)
Ø 4.8
(0.19)
Dimensions are in millimeters and (inches).
Front View
0.68 N•m
(6.0 lb•in)
2
3
4
5
6
7
Mounting Panel
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 21
Installing the HIM Chapter 2
3. Insert the supplied 3 m/9.8 ft. long 1202-C30 HIM cable into the mating
socket on the back of the HIM.
4. Install the supplied O-ring into the cable routing hole on the panel to
protect the cable.
5. Route the HIM cable through the cable routing hole on the panel.
6. Align the six threaded studs of the HIM with the panel clearance holes,
and place the HIM against the panel.
7. Tighten the nuts onto the six threaded studs of the HIM extending behind
the panel.
Recommended torque is 0.68 N•m (6.0 lb•in).
8. Route the HIM cable to the drive.
9. Connect the HIM cable to the DPI Port 2 on the drive as shown on
page 16
for a PowerFlex 750-Series drive or a PowerFlex 7-Class drive.
Removing the HIM
Remove the HIM from the drive HIM bezel or the remote-mount HIM bezel in
reverse order of how it was installed.
ATTENTION: Risk of injury or equipment damage exists. If the HIM cable or
remote-mount HIM bezel cable is disconnected from DPI Port 2 on the drive, the
drive may fault. Determine how the drive will respond before disconnecting the
cable.
IMPORTANT
The Host drive can remain powered when removing the HIM. However, a fault
will occur if the HIM is not the last controlling device and does not have Manual
control of the Host drive. To avoid a fault in this case, access the HIM Control
screen (shown on page 30
), press the key, and then remove the HIM
from the Host drive.
22 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 2 Installing the HIM
Notes:
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 23
Chapter 3
HIM Components
This chapter describes the components of the HIM.
HIM Keypad
The keypad consists of soft keys, navigation and number keys, and single-function
keys, which are described in their respective subsections that follow.
Soft Keys
The soft keys on the HIM are located at the top of the keypad and highlighted
below. Depending on the screen being displayed or the data entry mode being
used, a soft key name and its function changes. When a dynamic soft key (up to a
maximum of five keys) is active, its present function and corresponding Soft Key
Label (Figure 3
) is shown at the bottom of the HIM screen. For a list of possible
soft keys, their names, and corresponding functions, see Soft Key Labels
on
page 27.
Topic Page
HIM Keypad 23
LCD Display Elements 26
Main Screens
28
24 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 3 HIM Components
Navigation and Number Keys
The five blue multi-function keys (2, 4, 5, 6, and 8) shown below are used to do the
following:
Enter their respective numeric value
Scroll menus/screens
Perform corresponding functions displayed in the Data Area (see page 26
)
The five gray number keys (0, 1, 3, 7, and 9) are used only to enter their respective
numeric value.
Multi-function Key Name Function
2/Down Arrow Enters the numeric value ‘2’.
Scrolls down to select an item.
4/Left Arrow Enters the numeric value ‘4’.
Scrolls left to select an item.
5/Enter Enters the numeric value ‘5’.
Displays the next level of a selected menu item.
Enters new values.
Performs intended actions.
6/Right Arrow Enters the numeric value ‘6’.
Scrolls right to select an item.
8/Up Arrow Enters the numeric value ‘8’.
Scrolls up to select an item.
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 25
HIM Components Chapter 3
Single-function Keys
There are four single-function keys, which are highlighted below and listed in the
table below. Each single-function key always performs only its dedicated
function.
Single-function Key Name Function
Start Starts the drive.
(1)
(1) During drive Start Up these keys are temporarily inactive.
Folders Accesses folders for parameters, diagnostics, memory functions,
preferences, and other tasks.
(1)
Controls Accesses jog, direction, auto/manual, and other control functions.
Stop Stops the drive or clears a fault.
This key is always active.
This key is controlled by drive parameter 307 [Start Stop Mode].
26 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 3 HIM Components
LCD Display Elements
The basic HIM screen is divided into three display zones, which are shown in
Figure 3
and described in their respective subsections that follow.
Figure 3 - HIM Display Zones
Status Bar
The Status Bar provides operating status information for the host drive.
Data Area
The Data Area displays the data or function presently being acted upon.
Status Bar
Data Area
Soft Key Labels
00
Stopped
0.00 Hz
AUTO
Host Drive
240V 4.2A
20G...D014
ESC REF TEXT
F
PAR#
Stopped
0.00 Hz
AUTO
F
Status Bar Element Meaning
Host Icon A small image of the connected host drive.
Stopped Status Text Indicates present host drive operating status.
Text flashes when a fault is present.
0.00 Hz Feedback Indicates drive output feedback (for example, Hz, RPM, amps, etc.)
AUTO/MAN Mode Indication Indicates Auto or Manual HIM status.
Alarm Indication Bell icon indicates that an alarm is present.
F or R (not shown) Rotation Indication Indicates Forward or Reverse direction of host drive operation.
DLX (not shown) DeviceLogix™ Indication Indicates when the host drive DeviceLogix feature is enabled.
Data Area Element Meaning
Host or Device Icon Image of the host drive or image of the device connected to the port
selected.
00
Port Selection Indicates selected port. Use the or navigation keys to
select a port.
Host Drive User-Definable Text Top line of text in the Data Area can be edited by the user.
00
Host Drive
240V 4.2A
20G...D014
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 27
HIM Components Chapter 3
Soft Key Labels
The Soft Key Labels identify the present function of a corresponding Soft Key on
the Key Pad. Different screens may show different Soft Key Labels.
ESC VIEW REF TEXTPAR#
Soft Keys
Soft Key Labels
Soft Key Label Name Function
. Decimal Point Adds decimal point to the right-most position of a numeric value.
Backspace Deletes the character to the left of the cursor.
+ / - Sign Changes the sign of a parameter value.
# Number Selects the Direct Numeric Entry Method to change PowerFlex® 750-Series drive parameter associations.
Language Directly accesses the Select Language To Use screen.
Scroll Up Scrolls up through display lines.
Increases a value.
Scroll Down Scrolls down through display lines.
Decreases a value.
Scroll Left Scrolls left through display lines.
Scroll Right Scrolls right through display lines.
ACK Acknowledge Acknowledges the fault or alarm on the popup screen, stops the backlight from flashing, and keeps the popup
screen active.
ALL All Clears all faults, alarms or events when a popup box appears from a queue screen.
Restores all Host or Port device parameters to factory defaults.
CLR Clear Deletes an entire text string.
Displays the Select Action popup box used to clear the selected fault, alarm or event, or the entire fault, alarm
or event queue.
DEL Delete Deletes a highlighted character.
EDIT Edit Accesses a displayed parameter to edit.
Accesses the Edit Process Display screen.
END End Displays the end (least recent) fault, alarm or event in a queue
Scrolls to the end line of data on the Device Version information screen.
ENTER Enter Displays the next level of a selected menu item.
Enters new values.
Performs the intended action.
ESC Escape Cancels port verification conflict popup box during procedure to resolve a conflict.
Cancels the existing screen and returns to the previous screen.
Cancels an entry.
Cancels popup Fault Display screen.
Displays the time zone groups list screen (only when the Date/Time Set Edit Mode screen is shown).
EXP Exponent Allows data entry using scientific notation for 32-bit REAL (floating point) values.
FIX Fix Fixes ‘Changed’ or ‘Requires Configuration’ port verification conflicts upon power up.
INFO Information Shows additional information about a selected port verification conflict upon power up.
Shows additional information about Set Default actions.
INS Insert Inserts a space to the left of a highlighted character.
LINK Link Displays a Link Edit popup box to link parameters (only PowerFlex 7-Class drives).
LOWER L
ower Displays the lower 16 bits (bits 0…15) of a 32-bit Bit-type parameter.
28 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 3 HIM Components
Main Screens
The HIM main screens include the Status screen, Process screen, Control screen,
Folder screens, and Fault Display screens, which are described in their respective
subsections that follow.
Status Screen
On power up, the Status screen (Figure 4) is shown by default. Depending on the
type of host drive, the Status screen displays the following information.
Figure 4 - Example Status Screens
MOST Most Restores most Host or Port device parameters to factory defaults.
PAR# Parameter Number Navigates directly to a parameter.
PGDN Page Down Scrolls down to the next page of data lines on the Device Version information screen.
PGUP Page Up Scrolls up to the previous page of data lines on the Device Version information screen.
REF Reference Enters the speed reference for the Host Drive.
RESET Reset Resets the Process screens displayed monitoring items to the factory default monitoring items listed on page 38
.
TEXT Text Edits user-definable text for the device selected.
TOP To p Displays the top (most recent) fault, alarm or event in a queue.
Scrolls to the top line of data on the Device Version information screen.
UPPER Upper Displays the upper 16 bits (bits 16…31) of a 32-bit Bit-type parameter.
VIEW View Toggles between select screens and views.
Displays the time stamp screen from a fault, alarm or event queue screen.
ZONES Zones Displays the Select Time Zone screen.
Soft Key Label Name Function
Displayed Information
Host PowerFlex Drive
750-Series 7-Class
Selected device icon and port number
??
Device name
(1)
(1) The displayed default device name is dependent on the host drive. The device name can be
changed, for example, to Host Drive as shown in the screens below. See Creating a User-Defined
Drive/Peripheral Name on page 37 for details.
??
Rating text (volts, amps)
??
Drive catalog text
?
not applicable
Firmware revision and hardware series
(2)
(2) The firmware version and hardware series for a PowerFlex 750-Series drive can be shown using
HIM menu screens. For details, see Checking Drive and Peripheral Firmware Revisions on page 49
.
?
For PowerFlex 750-Series Drive For PowerFlex 7-Class Drive
00
Stopped
0.00 Hz
AUTO
Host Drive
240V 4.2A
20G...D014
ESC REF TEXT
F
PAR#
00
Stopped
0.00 Hz
AUTO
Host Drive
240V 4.2A
Rev 3.002 Ser. A
ESC REF TEXT
F
PAR#
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 29
HIM Components Chapter 3
Status Screen Soft Keys
Status Screen Navigation/Number Keys
If you would rather see the Process screen (shown below) as the initial power-up
screen, change the HIM Parameter 03 - [Initial Screen] value to ‘1’ (Process
Scrn). By default, when the HIM keys are not used for the time period set in
Parameter 07 - [User Dspy Time], the screen being displayed at that time will
revert back to the initial screen. You can disable this feature by setting Parameter
06 - [User Dspy Enable] to ‘1’ (Disable).
Process Screen
Note: The PowerFlex 755T products do not fully support Process Display text.
To display the Process screen, press the ESC soft key on the Status screen
(Figure 4
). The Process screen shows various drive monitoring parameters. Multi-
line and Single-line views can be selected by pressing the VIEW soft key. The
displayed default monitoring parameters can be changed. See Customizing the
Process Screen on page 38 for details.
Process Screen Soft Keys
Label Name Function
ESC Escape Toggles between the Status and Process Display screens.
Language Icon Directly accesses the Select Language To Use screen.
REF Reference Enters the speed reference for the Host Drive.
PAR# Parameter Number Directly accesses a parameter for the device on selected port. (This soft key is
not available if the device has no parameters.)
TEXT Text Edits user-definable text for the device on selected port.
Key Name Function Screen Element
4/Left Arrow Selects the device on previous port.
6/Right Arrow Selects the device on next port.
Label Name Function
ESC Escape Toggles between the Process Display and Status screens.
VIEW View Toggles between the multi-line and single-line views.
REF Reference Enters the speed reference for the Host Drive.
PAR# Parameter Number Directly accesses a parameter for the selected port device.
EDIT Edit Directly accesses the Edit Process Display screen.
00
Stopped
0.00 Hz
AUTO
0.00
0.000
0.00
VIEW
F
REF PAR#
Amps
Bus VDC
Out Vlts
EDITESC
30 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 3 HIM Components
Process Screen Navigation/Number Keys
Control Screen
The Control screen (shown below) is used to directly control the drive. It displays
vertical bar graphs of the drives speed Reference and Feedback values, and a Key
Function Map that corresponds to the navigation/number keys for drive control.
Press the (Controls) key to display the Control screen.
Control Screen Soft Key
Control Screen Navigation/Number Keys
Key Name Function Screen Element
8/Up Arrow Scrolls up through the display lines.
2/Down Arrow Scrolls down through the display lines.
IMPORTANT
To navigate from the Control screen to another HIM menu screen, you must
always press the ESC soft key to deactivate the Control screen and display the
previous screen.
Label Name Function
ESC Escape Deactivates the Control Screen and reverts back to the previous screen.
Label Key Function
JOG Jogs the host drive.
REF
Decreases the speed reference for the host drive.
HELP Displays Rockwell Automation Drives Technical Support direct phone number, website
address, and email address.
REV Sets the direction to reverse for the host drive.
EDIT
REF
Allows direct data entry of the speed reference for the host drive.
FWD Sets the direction to forward for the host drive.
REMOVE
HIM
Allows HIM removal without causing a fault if the HIM is not the last controlling device.
(The REMOVE HIM label is not available when the HIM has manual control of the host
drive. In this case, a fault will occur if the HIM is removed.)
REF
Increases the speed reference for the host drive.
MANUAL Switches between Auto and Manual modes.
ESC
REF
MANUAL
FBKREF
REMOVE
HIM
EDIT
REF
FWDREV
REF
JOG HELP
Control Screen Key Function Map
corresponds to Navigation/Number Keys
See table below
for key functions
Stopped
0.00 Hz
AUTO
F
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 31
HIM Components Chapter 3
Folder Screens
The drive and each connected peripheral has its own set of Folder screens:
To display the last-viewed Folder screen, press the (Folders) key. The Folder
screen Data Area displays:
Selected device and port number
Host drive and peripheral folders
Figure 5 - Example Folder Screen (Device Parameters)
Folder Screen Soft Key
Folder Screen Navigation/Number Keys
Folder Screen Description
PORTS Displays a list of host drive ports to which peripherals are connected. The host drive is always Port
00. An icon appears for the device occupying the selected port.
DEV PARAM Displays a list of available methods to access the devices parameters.
HOST PARAM
(1)
(1) The HOST PARAM folder screen is only available for PowerFlex 750-Series peripherals that support use of Host Drive parameters (for
example, the 20-750-DNET DeviceNet network communication option module).
Displays a list of available methods to access the host drive parameters.
DIAGNOSTIC Displays a list of available diagnostic information items for the device.
MEMORY Displays a list of available memory storage items for the device.
PROPERTIES Displays a list of available user-defined convenience functions for the device.
START UP Displays a list of available host drive start-up routines. This folder is not applicable for peripheral
devices and is not shown.
Label Name Function
ESC Escape Reverts back to the Status or Process Display screen.
Key Name Function Screen Element
2/Down Arrow Scrolls down through the folder items.
4/Left Arrow Scrolls to the previous folder.
5/Enter Displays the next level screen for a selected folder item. Not applicable
6/Right Arrow Scrolls to the next folder.
8/Up Arrow Scrolls up through the folder items.
00
ESC
DEV PARAM
Linear List
File-Group
Changed Parameters
Param Access Level
Stopped
0.00 Hz
AUTO
F
32 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 3 HIM Components
Fault Display Screen
The popup Fault Display screen automatically appears when a fault condition is
detected for the host drive or any connected peripheral. The popup Fault Display
screen flashes to alert that a fault condition exists. The Fault Display screen
(example shown below) provides the following information:
Fault Code number
Fault description
Elapsed time (in hh:mm:ss format) from fault detection
The flash mode for the Fault Display screen can be changed. For details, see
Setting Display Flashing for Fault Indication on page 42
.
Fault Display Screen Soft Keys
Fault Display Screen Single Function Key
Label Name Function
ESC Escape Reverts back to the previous screen without clearing the fault.
CLR Clear Removes the popup Fault Display screen from the display and clears the fault.
Key Name Function
Stop Removes the popup Fault Display screen from the display, clears the fault, and
sends a STOP command to the Host drive.
Fault Code 81
DPI Port1 Loss
Elapsed Time 01:26:37
CLR
– – FAULTED – –
Stopped
0.00 Hz
AUTO
F
ESC
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 33
Chapter 4
Using the HIM
This chapter provides information about using the HIM.
For a list of parameters, see Appendix B
, HIM Parameters.
Initial HIM Operation on New
Drive Powerup
When powering up a new drive for the first time, the HIM runs through an
initial operating routine that does the following:
Prompts you to select a language.
Initiates a drive start-up routine.
Initiates a port verification check (only for PowerFlex® 750-Series drives).
If a port conflict is detected, see page 62
for information to resolve it.
Topic Page
Initial HIM Operation on New Drive Powerup 33
Selecting Display Contrast 34
Setting the Date/Time for PowerFlex 750-Series Drives
35
Creating a User-Defined Drive/Peripheral Name 37
Customizing the Process Screen 38
Resetting the Drive/Peripherals
40
Setting Factory Defaults 40
Setting Display Flashing for Fault Indication 42
Setting Display Flashing for Alarm Indication
43
Viewing/Editing Drive or Peripheral Parameters 44
Viewing/Clearing Drive Faults or Alarms 46
Viewing Peripheral Diagnostic Items
47
Viewing/Clearing Peripheral Events 48
Checking Drive and Peripheral Firmware Revisions 49
Using the CopyCat Function
50
Changing PowerFlex 750-Series Drive Parameter Associations 54
Linking Parameters in PowerFlex 700/700S Drives 57
Using a
n Access Code 59
Initiating PowerFlex 750-Series Drive Port Verification
62
Changing Language for the Display Text 64
Updating the HIM Firmware or Language
65
34 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 4 Using the HIM
Selecting Display Contrast
The contrast of the HIM display can be adjusted for optimal viewing. Follow
these steps to change the contrast.
1. Access the Status screen, which is displayed on HIM power up.
Figure 6 - Status Screen
2. Use the or key to scroll to the port to which the HIM is
connected.
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the PROPERTIES folder.
5. Use the or key to select Adjust Contrast.
6. Press the (Enter) key to display the Set LCD Contrast edit popup
box.
7. Use the or soft key to adjust contrast to the desired setting.
8. Press the ESC soft key to set the contrast and exit the screen.
Port Location
01 HIM cradle on the front of the drive.
02 DPI™ port near the bottom of the drive control pod (PowerFlex 750-Series drives) or
at the bottom of the drive (PowerFlex 7-Class drives).
03 Splitter cable port when the cable is plugged into the DPI port near the bottom of the drive control
pod (PowerFlex 750-Series drives) or at the bottom of the drive (PowerFlex 7-Class drives).
00
Stopped
0.00 Hz
AUTO
Host Drive
240V 4.2A
20G...D014
ESC REF TEXT
F
PAR#
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 35
Using the HIM Chapter 4
Setting the Date/Time for
PowerFlex 750-Series Drives
The PowerFlex 750-Series drive has a real-time clock which supports its time
stamp feature for faults and alarms. This clock must be accurately set to provide
meaningful time stamp data. Follow these steps to set the date and time.
1. Access the Status screen (see Figure 6
).
2. If Port 00 (host drive) is not shown above the ESC soft key, use the
or key to scroll to Port 00.
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the PROPERTIES folder.
5. Use the or key to select Set Date and Time.
6. Press the (Enter) key to display the Date/Time Set screen.
The top line shows the present date and time in this format:
yyyy/mm/dd hh:mm:ss
Note that the time is always displayed in a 24-hour format. For example,
6:00 pm is shown as 18:00:00.
7. Press the EDIT soft key to access the Date/Time Set Edit Mode screen,
which highlights the present time zone line.
8. To select the time zone:
a. Press the ZONES soft key to display the Select Time Zone screen.
b. Use the or key to select your time zone region (for
example, Americas).
c. Press the (Enter) key to enter your selection.
d. Use the or key to select your specific time zone (for
example, Chicago).
IMPORTANT
The information in this section does not apply to PowerFlex 7-
Class drives.
AUTO
ESC EDIT
F
Port 00 Date / Time Set
Monday 2008/05/12 10:38:47
(GMT-06:00) Chicago
Stopped
0.00 Hz
AUTO
ESC ZONES
F
Stopped
0.00 Hz
?
Port 00 Date / Time Set
Monday 2008/05/12 10:38:47
(GMT-06:00) Chicago
36 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 4 Using the HIM
e. Press the (Enter) key to enter your selected time zone.
9. To set the date:
a. Press the soft key to select the year in the top line.
b. Use the numeric keys to enter the correct year.
c. Press the soft key to select the month in the top line.
d. Use the numeric keys to enter the correct month.
e. Press the soft key to select the day in the top line.
f. Use the numeric keys to enter the correct day.
10. To set the time:
a. Press the soft key to select the hour in the top line.
b. Use the numeric keys to enter the correct hour.
c. Press the soft key to select the minutes in the top line.
d. Use the numeric keys to enter the correct minute.
e. Press the soft key to select the seconds in the top line.
f. Use the numeric keys to enter the correct seconds.
11. Press the ESC soft key to return to the previous screen.
TIP
To delete an erroneous date (or time) entry, use the soft key. Also, a
partial or complete date (or time) value will not update until you press
the soft key to advance to another field or press the ESC soft key to
return to the previous screen.
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 37
Using the HIM Chapter 4
Creating a User-Defined
Drive/Peripheral Name
Note: The PowerFlex 755T products do not fully support User Defined text.
The host drive and each of its connected peripherals has a default name. You can
change any of these default names, but each new user-defined name cannot
exceed 16 characters in length. Follow these steps to change a default name.
1. Access the Status screen (see Figure 6
).
2. Use the or key to scroll to the Port of the device whose name
you want to change (for example, Port 00 for the host drive).
3. Press the TEXT soft key to display the Edit User Defined Text popup box.
4. Use the or key to move the cursor to the desired character
position in the displayed name.
5. Press the key to access the last-viewed character set.
6. Press the appropriate numeric key to access the desired character set.
Also, use the appropriate soft keys to help create the new name.
7. With the desired character selected in that character position, press the
key to select and enter the character.
8. Repeat steps 4 through 7 for each character position.
9. When the desired name is displayed on the edit popup box, press the
ENTER soft key to enter and save the new name.
IMPORTANT
Text editing is not supported when using Asian language characters. Only
characters in the ISO 8859-1 Latin 1 Character Set, which is supported by U.S.
and European personal computers, are available. If a software tool is used for
text editing Asian characters, the HIM will replace all unsupported characters
with a [] (narrow rectangle) mark.
Numeric Key Function
Selects the numeric character set.
Selects the symbols character set.
Selects the upper case letter character set.
Selects the lower case letter character set.
Soft Key Function
DEL Deletes a highlighted character.
INS Inserts a space to the left of a highlighted character.
CLR Deletes an entire text string.
E S C ENTER
Stopped
0.00 Hz
AUTO
F
INS DEL
,=Move Cursor =Char Set
CLR
Edit User Defined Text
PowerFlex 755
38 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 4 Using the HIM
Customizing the Process
Screen
Note: The PowerFlex 755T products do not fully support Process Display text.
Do not use this feature with these products.
The Process screen can be displayed as a multi-line or single-line view screen, and
can be customized to show different drive monitoring items, apply a scale factor,
or change text for the displayed drive parameter. These modifications are
described in their respective subsections that follow.
Selecting Multi-Line or Single-Line View
By default, the Process screen shows a multi-line view of these drive monitoring
items.
Figure 7 - Multi-Line View Process Screen
1. Press the ESC soft key until the Process screen appears.
2. For PowerFlex 750-Series drives only, use the or key to scroll
to the hidden line items on the multi-line view screen.
3. To change the multi-line view Process screen to show each of the drive
monitoring items in a larger single-line view, press the VIEW soft key.
4. Use the or key to scroll to each single-line view Process screen.
Figure 8 - Single-Line View Process Screen Examples
5. To return to the multi-line view Process screen, press the VIEW soft key
again.
Drive Monitoring Item Host PowerFlex Drive
Screen Text Description 750-Series 7-Class
Amps Output amps
??
Bus DC DC Bus Volts
??
Out Vlts Output Volts
?
not applicable
Out Pwr Output Power
?
Elp kWHr Elapsed kWHr
?
Trq Cur Torque Current
?
0.00
0.000
0.00
Stopped
0.00 Hz
AUTO
F
ESC VIEW REF PAR#
Amps
Bus VDC
Out Vlts
EDIT
For PowerFlex 750-Series Drive
0.00
0.000
Stopped
0.00 Hz
AUTO
F
ESC VIEW REF PAR#
Amps
Bus VDC
EDIT
For PowerFlex 7-Class Drive
0.00
Stopped
0.00 Hz
AUTO
F
ESC VIEW REF PAR#
Amps
0.000
Stopped
0.00 Hz
AUTO
F
ESC VIEW REF PAR#
Bus VDC
0.00
Stopped
0.00 Hz
AUTO
F
ESC VIEW REF PAR#
Out Vlts
EDIT EDIT EDIT
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 39
Using the HIM Chapter 4
Changing Displayed Items, Adding a Scale Factor, or Customizing Text
You can further customize the Process screen by:
Changing a displayed parameter to a different parameter.
Applying a scale factor to the displayed parameter.
Customizing text for the displayed parameter.
To do any or all of the above modifications, follow these steps.
1. With either the multi-line view Process screen (Figure 7
) or the single-line
view Process screen (Figure 8
) displayed, use the or key to
select the drive monitoring item you want to change.
2. Press the EDIT soft key.
For example, suppose you want to change the first drive monitoring item.
In this case, the Process Display 1 Edit screen is shown.
3. Use the soft key to select what you want to change (parameter, scale, or
text) for the drive monitoring item.
4. Press the EDIT soft key to display its respective edit popup box (see
examples below).
5. For parameter or scale editing, use the numeric keys and available soft keys,
and press the ENTER soft key to enter and save the item.
For text editing, use the numeric keys, available soft keys, and the key
to enter each character. Then press the ENTER soft key to enter and save
the complete text string.
AUTO
ESC EDIT
F
Stopped
0.00 Hz
?
Port 00 Proc Display 1
Param: 7 Output Current
Scale:+/- 1.00
Text: Amps
Value: 0.00 amps
RESET
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
Edit Proc Dspy 1 Param
7
1 << 1474
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
Edit Proc Dspy 1 Scale
1.00
0.00 << 300.00
ES C ENTER
Stopped
0.00 Hz
AUTO
F
INS DEL
,=Move Cursor =Char Set
CLR
.
Edit Proc Dspy 1 Text
Amps
40 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 4 Using the HIM
Resetting the Drive/
Peripherals
The drive or any of its connected peripherals can be reset by removing and
restoring power to the drive (power cycling). If this is not convenient or cannot
be done because of application circumstances, the HIM can be used to reset the
drive/peripherals. Follow these steps to reset the drive or any of its peripherals.
1. Access the Status screen (see Figure 6
).
2. Use the or key to scroll to the Port of the device you want to
reset (for example, Port 00 for the host drive).
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the DIAGNOSTIC folder.
5. Use the or key to select Reset Device.
6. Press the (Enter) key to display a popup box asking if you want to
reset the device.
7. Press the ENTER soft key to affirm and reset the device, or press the ESC
soft key to cancel.
Setting Factory Defaults
The procedure to set a PowerFlex 750-Series drive and its connected peripherals
to factory defaults is slightly different than the procedure used for a PowerFlex 7-
Class drive and its peripherals. See the respective subsection for instructions.
Setting PowerFlex 750-Series Drives/Peripherals to Factory Defaults
1. Access the Status screen (see Figure 6).
2. Use the or key to scroll to the Port of the device whose
parameters you want to set to factory defaults (for example, Port 00 for the
host drive or the respective port number for one of the drive’s connected
peripherals).
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the MEMORY folder.
5. Use the or key to select Set Defaults.
6. Press the (Enter) key to display the Set Defaults popup box (see
examples below).
Stopped
0.00 Hz
AUTO
ESC
F
Port 00 Set Defaults
Host and Ports (Preferred)
This Port Only
INFO
Stopped
0.00 Hz
AUTO
ESC
F
Port xx Set Defaults
This Port Only
INFO
For Host Drive
For Connected Peripheral
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 41
Using the HIM Chapter 4
7. Use the or key to select the appropriate action.
Host and Ports (Preferred): Selects the host device and all ports for a
factory default action.
•This Port Only: Selects only this port for a factory default action.
8. Press the (Enter) key to display the warning popup box to reset
defaults.
Setting PowerFlex 7-Class Drives/Peripherals to Factory Defaults
1. Access the Status screen (see Figure 6).
2. Use the or key to scroll to the Port of the device whose
parameters you want to set to factory defaults (for example, Port 00 for the
host drive or the respective port number for one of the drive’s connected
peripherals).
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the MEMORY folder.
5. Use the or key to select Set Defaults.
6. Press the (Enter) key to display the Set Defaults popup box.
7. Press the ENTER soft key to affirm and set all device parameter values to
factory defaults—or press the ESC soft key to cancel.
TIP
For a description of a selected menu item, press the INFO soft key.
Figure 9 - ‘Host and Ports (Preferred)’ Popup Box
Press the ENTER soft key to affirm and set most parameters
for the host drive and port devices to factory defaults. In this
case, see the host drive and port device documentation for
the settings that will not be restored—or press the ESC soft
key to cancel.
Figure 10 - ‘This Port Only’ Popup Box
Press the MOST soft key to set most settings for the selected port
device to factory defaults. In this case, see the host drive
documentation for the settings that will not be restored. Press
the ALL soft key to set all settings for the selected port device to
factory defaults—or press the ESC soft key to cancel.
Stopped
0.00 Hz
AUTO
F
WARNING
Sets most parameters in the
Host device and all ports
to factory defaults.
Continue?
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
MOSTALL
WARNING
Use MOST to reset typical
?
settings on this port
(preferred). Use ALL to
reset all settings.
?
ESC
Stopped
0.00 Hz
AUTO
F
WARNING
Sets all parameters to
factory defaults.
Continue?
ESC
ENTER
42 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 4 Using the HIM
Setting Display Flashing for
Fault Indication
Whenever a fault for the host drive or any of its connected peripherals is
detected, a popup Fault Display screen (see page 32
) appears. By default, only the
Status Bar flashes to alert the operator. However, you can change the flash mode
for the Fault Display screen to one of the following modes:
Flash Bklite; selects the entire LCD screen to flash.
Flash Status (default); selects only the Status Bar (item 1, Figure 3
) to flash.
Flash None; selects no flashing for the Fault Display screen.
Follow these steps to change the flash mode for the Fault Display screen.
1. Access HIM Parameter 04 - [Fault Dspy Type] using either the Direct
Parameter Access method (page 44
) or Alternate Linear List method
(page 45
).
2. Press the EDIT soft key to display the Edit Fault Dspy Type popup box.
3. Use the and soft keys to select the desired flash mode. To delete an
erroneous entry, use the soft key.
4. Press the ENTER soft key to enter your selection and return to the
parameter screen.
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
??
Edit Fault Dspy Type
Flash Bklite 0
0<<2
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 43
Using the HIM Chapter 4
Setting Display Flashing for
Alarm Indication
Whenever an alarm for the Host Drive is detected, an alarm bell icon appears in
the Status Bar. By default, only the Status Bar flashes to alert the operator.
However, you can change the flash mode for alarm indication to one of the
following modes:
Flash Bklite; selects the entire LCD screen to flash.
Flash Status (default); selects only the Status Bar (item 1, Figure 3
) to flash.
Flash None; selects no flashing for alarm indication.
Follow these steps to change the flash mode for alarm indication.
1. Access HIM Parameter 05 - [Alarm Dspy Type] using either the Direct
Parameter Access method (page 44
) or Alternate Linear List method
(page 45
).
2. Press the EDIT soft key to display the Edit Alarm Dspy Type popup box.
3. Use the and soft keys to select the desired flash mode.
To delete an incorrect entry, use the soft key.
4. Press the ENTER soft key to enter your selection and return to the
parameter screen.
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
??
Edit Alarm Dspy Type
Flash Status 1
0<<2
44 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 4 Using the HIM
Viewing/Editing Drive or
Peripheral Parameters
The PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM can show host drive
parameters in a File-Group-Parameter view or by Linear List. To access drive or
peripheral parameters for viewing or editing, use either the direct parameter
access method or the alternate linear list access method. See the respective
subsections that follow for instructions.
Selecting File-Group-Parameter or Linear List View
Follow these steps to change viewing between File-Group-Parameter and Linear
List.
1. Access the Status screen (see Figure 6
).
2. Use the or key to scroll to the Port of the device whose
parameters you want to access (for example, Port 00 for the host drive).
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the DEV PARAM or HOST
PARAM folder.
5. Use the or key to select Linear List or File-Group.
6. Press the (Enter) key to display the last-viewed or first parameter in
the Linear List, or the last-viewed or first parameter in the first Group.
Direct Parameter Access Method
1. Access the Status screen (see Figure 6).
2. Use the or key to scroll to the Port of the device whose
parameters you want to access (for example, Port 00 for the host drive).
3. Press the PAR# soft key to display the Jump to Param # entry popup box.
4. Use the numeric keys to enter the desired parameter number, or use the
or soft key to scroll to the desired parameter number.
5. Press the ENTER soft key to display the parameter.
TIP
Not all peripheral devices support viewing parameters in a File-Group-
Parameter view.
TIP
Some devices have two sets of parameters (Device and Host
parameters). In this case, a popup box will appear enabling you to first
choose the parameter set in which the parameter that you want to
access resides.
TIP
Pressing and holding the or soft key for 1 second or longer
provides continuous scrolling until you release the key.
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 45
Using the HIM Chapter 4
6. Press the EDIT soft key (for editable parameters only) to display the Edit
Parameter popup box.
Figure 11 - Example Edit Parameter Popup Box
7. Use the numeric keys, decimal soft key, and soft key to edit the parameter.
8. Press the ENTER soft key to enter the new parameter value and return to
the parameter screen.
Alternate Linear List Access Method
1. Access the Status screen (see Figure 6).
2. Use the or key to scroll to the Port of the device whose
parameters you want to access (for example, Port 00 for the host drive).
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the PARAMETER folder.
5. Use the or key to select Linear List.
6. Press the (Enter) key to display either the device’s last-viewed
parameter or the first parameter in the linear list.
7. Use the or key to scroll to the desired parameter.
8. Press the EDIT soft key (for editable parameters only) to display the Edit
Parameter popup box (Figure 11
).
9. Use the numeric keys, decimal soft key, and soft key to edit the parameter.
10. Press the ENTER soft key to enter the new parameter value and return to
the parameter screen.
TIP
When the decimal soft key is pressed while editing a numeric value,
this key temporarily changes to an EXP soft key to allow exponential
entry.
TIP
When the decimal soft key is pressed while editing a numeric value,
this key temporarily changes to an EXP soft key to allow exponential
entry.
Edit Accel Time 1
5.0 Secs
0.00 << 3600.00
ESC
.
Stopped
0.00 Hz
AUTO
F
ENTER
46 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 4 Using the HIM
Viewing/Clearing Drive
Faults or Alarms
Follow these steps to view/clear drive faults or alarms.
1. Access the Status screen (see Figure 6
).
2. If Port 00 (host drive) is not shown above the ESC soft key, use the
or key to scroll to Port 00.
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the DIAGNOSTIC folder.
5. Use the or key to select Faults or Alarms.
6. Press the (Enter) key to display the numbered fault/alarm queue.
Faults/alarms are listed from the most recent to occur (line 01) to the least
recent. The fault/alarm number and name are shown at the right.
7. Use the or key or the following soft keys to navigate within
the fault/alarm queue.
8. To clear faults/alarms, press the CLR soft key.
In the Select Action popup box, select the appropriate action using the
or key and press the (Enter) key to clear the active
fault/alarm or clear the fault/alarm queue. To cancel the popup box, press
the ESC soft key or select Cancel from the list and press the (Enter)
key.
Soft Key Function
ENTER Displays the Time Stamp popup box for the fault/alarm. Note that the real-time clock in a
PowerFlex 750-Series drive must be accurately set to provide meaningful time stamp data. For
details, see Setting the Date/Time for PowerFlex 750-Series Drives on page 35.
Use the or
key to scroll to all parameters related to the displayed fault/alarm
(if supported by device).
TOP Displays the first (most recent) fault/alarm in the queue.
END Displays the last (least recent) fault/alarm in the queue.
Faulted
0.00 Hz
AUTO
ESC TOP END
F
CLR
Port 00 Faults
01 82 Port 2 DPI Loss
02 49 Drive Powerup
03 9 Trnsistr OvrTemp
04 8 Heatsink OvrTemp
ENTER
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 47
Using the HIM Chapter 4
Viewing Peripheral
Diagnostic Items
If you encounter unexpected communication problems, diagnostic items for the
drive’s connected peripherals—including the HIM—can help you or Rockwell
Automation personnel troubleshoot the problem. Follow these steps to view
peripheral diagnostic items.
1. Access the Status screen (see Figure 6
).
2. Use the or key to scroll to the Port of the device whose
diagnostic items you want to view (for example, Port 02 for the connected
HIM).
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the DIAGNOSTIC folder.
5. Use the or key to select Diagnostic Items.
6. Press the (Enter) key to display either the device’s last-viewed
diagnostic item or the first diagnostic item in the list.
Tab l e 1
shows all possible Diagnostic Items for the HIM. To view the HIM
Diagnostic Items, use the procedure described above.
Table 1 - 20-HIM-A6 and 20-HIM-C6S HIM Diagnostic Items
No. Name Description
1 LCD Contrast The present value of the HIM LCD contrast level, and ability to set the contrast level
from this screen.
2 Common Logic Cmd The present value of the Common Logic Command being transmitted to the drive by
the HIM.
3 Prod Logic Cmd The present value of the Product Specific Logic Command being transmitted to the
drive by the HIM.
4 Common Logic Sts The present value of the Common Logic Status being received from the drive by the
HIM.
5 Prod Logic Sts The present value of the Product Specific Logic Status being received from the drive by
the HIM.
6 Reference The present value of the Product Specific Reference being transmitted to the drive by
the HIM.
7 Feedback The present value of the Product Specific Feedback being received from the drive by
the HIM.
8 Boot Flash Count The present value of the Boot Flash Counter.
9 App Flash Count The present value of the App Flash Counter.
48 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 4 Using the HIM
Viewing/Clearing Peripheral
Events
Events for the host drive’s connected peripherals—including the HIM—are
logged into their respective event queues. Many events in an event queue occur
under normal operation. If you encounter unexpected problems, the events may
help you or Allen-Bradley personnel troubleshoot the problem. Follow these step
to view or clear the events of a connected peripheral.
1. Access the Status screen (see Figure 6
).
2. Use the or key to scroll to the Port of the device whose events
you want to view (for example, Port 06 for a network communication
option module).
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the DIAGNOSTIC folder.
5. Use the or key to select Events.
6. Press the (Enter) key to display the device’s numbered event queue.
Events are listed from the most recent to occur (line 01) to the least recent.
The event number and name are shown at the right.
7. Use the or key or the following soft keys to navigate within
the event queue.
8. To clear events, press the CLR soft key.
In the Select Action popup box, select the appropriate action using the
or key and press the (Enter) key to clear the event or
clear event queue. To cancel the popup box, press the ESC soft key or select
Cancel from the list and press the (Enter) key.
The PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM maintains an event queue that
reports the history of its actions. Table 2
shows all possible events for the HIM. To
view the HIM events, use the procedure described above.
Soft Key Function
ENTER Displays the Time Stamp popup box for the event. Note that the real-time clock in a PowerFlex
750-Series drive must be accurately set to provide meaningful time stamp data. For details,
see Setting the Date/Time for PowerFlex 750-Series Drives on page 35.
TOP Displays the first (most recent) event in the queue.
END Displays the last (least recent) event in the queue.
Stopped
0.00 Hz
AUTO
ESC TOP END
F
CLR
Port 06 Events
01 14 DPI Online 500k
02 26 SI Online
03 29 Net Link Up
04 4 EEPROM Sum Error
ENTER
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 49
Using the HIM Chapter 4
Table 2 - 20-HIM-A6 and 20-HIM-C6S HIM Events
Checking Drive and
Peripheral Firmware
Revisions
Follow these steps to check the firmware revision of the drive or its peripherals.
1. Access the Status screen (see Figure 6
).
2. Use the or key to scroll to the Port of the device whose firmware
revision you want to view (for example, Port 00 for the host drive).
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the DIAGNOSTIC folder.
5. Use the or key to select Device Version.
6. Press the (Enter) key to display device version information.
Code Event Description
1Reserved
2 Device Power Up A normal power up.
3 Device Reset The HIM was reset due to a manual reset command or program crash.
4 EEPROM CRC Error The HIM EEPROM Data Storage Device is corrupt.
5 App Updated The HIM application firmware has been updated.
6 Boot Updated The HIM boot firmware has been updated.
7 Watchdog Timeout A program crash has occurred.
8 DPI Bus Off A DPI Bus Off fault was detected.
9 DPI Ping Timeout A DPI Ping Timeout fault was detected.
10 DPI Port Invalid A DPI Port ID fault was detected.
11 DPI Port Changed A DPI Port Changed fault was detected.
12 DPI Host Reset The host has sent a reset message.
13 DPI Baud 125K The DPI data rate is detected at 125K bits/second.
14 DPI Baud 500K The DPI data rate is detected at 500K bits/second.
15 DPI Host Invalid The HIM will not connect to this type of host.
16 DPI Dup Port Another DPI device is already connected to this port.
17 DPI Type 0 Logon The DPI log on was completed successfully.
18 DPI Type 0 Time A DPI Type 0 Command has timed out.
19-23 Reserved
24 DPI Msg Timeout A message to a DPI device has timed out.
25 DPI Manual Reset A reset command was sent through a fault object.
Stopped
0.00 Hz
AUTO
ESC
F
PowerFlex 755
Product Revision 1.007
Product Ser Num 00000000
Product Series A
–Main Control Board
FW Revision 1.007
TOP END PGUP PGDN
50 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 4 Using the HIM
Using the CopyCat Function
PowerFlex 750-Series drives and PowerFlex 7-Class drives provide a CopyCat
function that enables you to upload individual parameter sets for the host drive
or any of its connected peripherals into the HIM. Furthermore, an Upload All
Ports function enables you to conveniently upload multiple parameter sets for the
host drive and all of its connected peripherals in one single file. In either case, this
information can then be used as backup or can be transferred to another drive or
peripheral device by downloading the file from the HIM’s memory.
The CopyCat function also enables you to rename or delete individual or
multiple parameter sets stored in the HIM.
The HIM can store up to 50 individual parameter sets or up to 5 multiple
parameter sets. Due to the memory capacity of the HIM, these maximums will
vary when storing combinations of individual and multiple parameter sets.
Generally, the upload or download transfer process manages all conflicts.
However, the download will stop and a text message will appear if any of the
following conditions exist:
A device mismatch, such as firmware revision, device type, or device series
is detected.
The drive is access code protected.
The drive is running.
You then have the option to completely stop the download or continue after
noting the discrepancy for the parameters that could not be downloaded. These
parameters can then be manually adjusted.
Creating CopyCat Files
1. Access the Status screen (see Figure 6).
2. Use the or key to scroll to the Port of the device whose
parameter set you want to copy (for example, Port 00 for the host drive).
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the MEMORY folder.
5. Use the or key to select HIM CopyCat.
TIP
The Upload All Ports and Download All Ports functions are only available for
the host drive (Port 00) due to their unique functionality.
IMPORTANT
When using the HIM with a PowerFlex 753 drive with firmware revision 1.05 or
earlier, or a PowerFlex 755 drive with firmware revision 1.10 or earlier, the
CopyCat function cannot upload/download DeviceLogix™ values for DLX Out xx
and DLX In xx parameters and DeviceLogix program routines. Drives with a
later firmware revision support this function, but the HIM does not support
screen formatting for the DeviceLogix program.
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 51
Using the HIM Chapter 4
6. Press the (Enter) key to display the CopyCat Files selection screen.
7. Use the or key to select the appropriate action and press the
(Enter) key to initiate that action.
8. With New File selected on the Select Upload File screen, press the
(Enter) key to create the file. A popup box will appear to confirm that the
CopyCat file was successfully created. Press the ENTER soft key to
complete the procedure.
When selecting an item row that is an existing CopyCat file—not a ‘New
File’ row—to create a new CopyCat file, an Overwrite popup box will
appear. Press the ENTER soft key to affirm and overwrite the existing
CopyCat file—or press the ESC soft key to cancel.
Renaming CopyCat Files
1. Access the Status screen (see Figure 6).
2. Use the or key to scroll to the Port of the device whose
CopyCat file you want to rename (for example, Port 00 for the host drive).
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the MEMORY folder.
5. Use the or key to select HIM CopyCat.
TIP
Before any CopyCat files are created, only the ‘CopyCat From Device to
HIM’ menu item is shown. When Port 00 for the Host Drive is selected
in Step 2, the ‘Upload All Ports’ menu item also appears.
TIP
When a CopyCat file is created, its default file name corresponds to the
device whose file is being copied. For example, a newly created
CopyCat file for a PowerFlex 755 drive has a default file name of
‘PowerFlex 755’.
IMPORTANT
Text editing is not supported when using Asian language characters. Only
characters in the ISO 8859-1 Latin 1 Character Set, which is supported by U.S.
and European personal computers, are available. If a software tool is used for
text editing Asian characters, the HIM will replace all unsupported characters
with a [] (narrow rectangle) mark.
Stopped
0.00 Hz
AUTO
ESC
F
Port 00 CopyCat Files
CopyCat from Device to HIM
CopyCat from HIM to Device
Delete CopyCat File
Rename CopyCat File
52 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 4 Using the HIM
6. Press the (Enter) key to display the CopyCat Files selection screen.
7. Use the or key to select Rename CopyCat File.
8. Press the (Enter) key to display the Select File To Rename popup
box.
9. Use the or key to select the file to be renamed.
10. Press the (Enter) key to display the Edit CopyCat File Text popup box.
11. Use the or key to move the cursor to the desired character
position in the displayed name.
12. Press the key to access the last-viewed character set.
13. Press the appropriate numeric key to access the desired character set.
Also, use the appropriate soft keys to help create the new name.
14. With the desired character selected in that character position, press the
key to select and enter the character.
15. Repeat steps 11 through 14 for each character position.
16. When the desired name is displayed on the edit popup box, press the
ENTER soft key to enter and save the new name.
Numeric Key Function
Selects the numeric character set.
Selects the symbols character set.
Selects the upper case letter character set.
Selects the lower case letter character set.
Soft Key Function
DEL Deletes a highlighted character.
INS Inserts a space to the left of a highlighted character.
CLR Deletes an entire text string.
Stopped
0.00 Hz
AUTO
ESC
F
Port 00 CopyCat Files
CopyCat from Device to HIM
CopyCat from HIM to Device
Delete CopyCat File
Rename CopyCat File
E S C ENTER
Stopped
0.00 Hz
AUTO
F
INS DEL
,=Move Cursor =Char Set
CLR
Edit CopyCat File Text
PowerFlex 755
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 53
Using the HIM Chapter 4
Deleting CopyCat Files
1. Access the Status screen (see Figure 6).
2. Use the or key to scroll to the Port of the device whose
parameter set you want to delete (for example, Port 00 for the host drive).
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the MEMORY folder.
5. Use the or key to select HIM CopyCat.
6. Press the (Enter) key to display the CopyCat Files selection screen.
7. Use the or key to select Delete CopyCat File.
8. Press the (Enter) key to display the Select File To Delete popup box.
9. Use the or key to select the file (or all files) to delete.
10. Press the (Enter) key to display the confirmation popup box.
11. Press the ENTER soft key to affirm and delete the selected CopyCat file, or
press the ESC soft key to cancel.
Another popup box will appear to confirm that the CopyCat file was
successfully deleted.
12. Press the ENTER soft key to affirm and complete the procedure.
Stopped
0.00 Hz
AUTO
ESC
F
Port 00 CopyCat Files
CopyCat from Device to HIM
CopyCat from HIM to Device
Delete CopyCat File
Rename CopyCat File
Stopped
0.00 Hz
AUTO
F
Select File To Delete
PowerFlex 755 Cfg
Delete All Files
ESC
54 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 4 Using the HIM
Changing PowerFlex 750-
Series Drive Parameter
Associations
PowerFlex 750-Series drives have special parameters (indirect selector parameters
and reference parameters) which are always associated with other parameters.
The values for these special parameters are actually pointers to other parameters
in the drive or to Host parameters in connected peripherals. To change a
parameter association, first access the indirect selector or reference parameter.
Second, select the port number of the device whose parameter you want to target
for association. Then, select the target parameter of that device. If the target
parameter is a bit parameter, you must also select the appropriate bit you want to
associate with the indirect selector or reference parameter.
Parameter associations can be changed using one of these methods:
Individual Screen Entry Method—where individual popup screens are
used to enter the required parameter association data.
Direct Numeric Entry Method—where the required parameter association
data is entered as a number string on a single popup screen.
The following example illustrates how to use each method to change a parameter
association. Suppose you want the drive speed reference to come from the
network controller via the embedded EtherNet/IP adapter on the Main Control
Board in a PowerFlex 755 drive.
Using Individual Screen Entry Method
1. Access the indirect selector or reference parameter whose association you
want to change (for this example, drive Parameter 545 - [Spd Ref A Sel] as
shown below).
In this example, the Port field is shown selected. Use the or
key to select the Port, Parameter, or Bit (if applicable) fields.
TIP
Depending on the indirect selector or reference parameter selected,
you may see more available ports in the list.
ESC EDIT
Stopped
0.00 Hz
AUTO
F
#
Port 00 Dev Param 545
Spd Ref A Sel
P00 P0871
Port PowerFlex 755
PAR#
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 55
Using the HIM Chapter 4
2. Press the EDIT soft key to display the edit popup box for the selected field
(in this case, the port number field).
3. Use the or key to scroll to the port number of the device
whose parameter you want to target for the association (for this example,
Port 00, where the speed Reference parameters for the available drive ports
are located).
4. Press the ENTER soft key to enter the selected port number.
The target parameter selection popup box appears (see example screen
below), showing a list of available target parameters that can be associated.
5. Use the or key to scroll to the target parameter you want to
associate.
For this example, we selected drive Parameter 877 - [Port 13 Reference]).
6. Press the ENTER soft key to enter the selected target parameter.
If the target parameter:
•Is not a bit parameter, the parameter association is now changed and
the indirect selector or reference parameter screen re-appears with the
associated parameter information shown.
•Is a bit parameter, a list of available bit numbers is displayed. Use the
or key to scroll to the bit number of the target parameter
you want to associate, and press the ENTER soft key. The parameter
TIP
The ‘Zero Speed’ setting may be available to select for specific
applications that require a safe-state speed Reference.
Stopped
0.00 Hz
AUTO
F
Edit Spd Ref A Sel
Select Port To Use
Zero Speed
Port 00 PowerFlex755
E S C ENTER
Stopped
0.00 Hz
AUTO
F
Edit Spd Ref A Sel
Select Param To Use
Par 0546 Spd Ref A Stpt
Par 0571 Preset Speed 1
Par 0572 Preset Speed 2
E S C ENTER
ESC EDIT
Stopped
0.00 Hz
AUTO
F
#
Port 00 Dev Param 545
Spd Ref A Sel
P00 P0871
Port PowerFlex 755
PAR#
56 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 4 Using the HIM
association is now changed and the indirect selector or reference
parameter screen re-appears with the associated parameter information
shown.
Using Direct Numeric Entry Method
1. Access the indirect selector or reference parameter whose association you
want to change (for this example, drive Parameter 545 - [Spd Ref A Sel] as
shown below).
2. With any field (port, parameter, or bit) selected, press the # soft key to
display the Direct Numeric Entry popup box.
3. Use the numeric keys to enter a number string that represents the target
parameters device port number, parameter number and, only when the
target parameter is a bit parameter, its bit number.
The number string format is PPpppp.bb, where:
PP = device port number
pppp = target parameter number
bb = bit number (only used when target parameter is a bit parameter)
4. Press the ENTER soft key to enter the number string and complete the
parameter association.
The indirect selector or reference parameter screen re-appears with the
associated parameter information.
ESC EDIT
Stopped
0.00 Hz
AUTO
F
#
Port 00 Dev Param 545
Spd Ref A Sel
P00 P0871
Port PowerFlex 755
PAR#
ESC EDIT
Stopped
0.00 Hz
AUTO
F
#
Port 00 Dev Param 545
Spd Ref A Sel
P00 P0871
Port PowerFlex 755
PAR#
Stopped
0.00 Hz
AUTO
F
Edit Spd Ref A Sel
871
0 << 159999
E S C ENTER
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 57
Using the HIM Chapter 4
Linking Parameters in
PowerFlex 700/700S Drives
Most parameter values are entered directly by the user. However, specific
parameters can be ‘linked’, so the value of one parameter becomes the value of
another. For example, the value of an analog input can be linked to an
acceleration time. Rather than entering an acceleration time directly (via the
HIM), the link allows the value to change by varying the analog input signal. This
can provide additional flexibility for advanced applications.
Each link has two components:
Source parameter—sender of information
Destination parameter—receiver of information
Most parameters can be a source of data for a link, except parameters that use an
integer value representing an ENUM (text selection). These are not allowed,
since the integer is not actual data (it represents a value). See the drive
documentation for a list of parameters that can be destinations. All links must be
established between equal data types (parameter value formatted in floating point
can only source data to a destination parameter value that is also a floating point).
Establishing a Link
1. Access a valid destination parameter to be linked (for example, the Accel
Time 1 parameter 140 for a PowerFlex 700 drive or parameter 32 for a
PowerFlex 700S drive).
2. Press the LINK soft key to display the Link popup box for that parameter.
3. Enter the source parameter number (for example, the Analog In1 Value
parameter 16 for a PowerFlex 700 drive or parameter 801 for a PowerFlex
700S drive) to which you want to link the destination parameter.
4. Press the ENTER soft key.
The destination parameter screen reappears with the respective source
parameter value now mapped over the destination parameter range, and is
shown in destination parameter units. In this example, the value for
Analog Input 1 is 10.000 volts for a PowerFlex 700 drive, and is shown as
10.0 seconds.
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
Link Accel Time 1
0
0 << 1179
ESC
Stopped
0.00 Hz
AUTO
F
Port 00 Dev Param #140
Accel Time 1
10.0 Secs
LINK PAR#
58 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 4 Using the HIM
Deleting an Established Link
Follow these steps to delete an established link.
1. Access the screen for the destination parameter.
2. Press the LINK soft key.
3. In the Link popup box, enter a value of zero.
4. Press the ENTER soft key to delete the established link.
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 59
Using the HIM Chapter 4
Using an Access Code
All parameter configuration settings for the drive and its connected peripherals
can be protected from unauthorized access by using an access code.
Setting/Changing the Access Code
1. Access the Status screen (see Figure 6).
2. If Port 00 (host drive) is not shown above the ESC soft key, use the
or key to scroll to Port 00.
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the PROPERTIES folder.
5. Use the or key to select Change Password.
6. Press the (Enter) key to display the Enter New Password popup box.
7. Use the numeric keys to enter a desired access code value.
Use the soft key to delete an erroneous entry.
For your convenience, write down your assigned access code and store it in
a safe place.
8. Press the ENTER soft key to enter the new access code.
9. After the access code verification screen appears, confirm the new access
code by re-entering its value.
Thereafter, the HIM immediately logs in to the drive, which is indicated
by the Log Out menu line in the PROPERTIES folder. All drive/
peripheral parameters are accessible to view or edit.
10. To initiate access code protection, do the following:
a. Use the or key to select Log Out from the PROPERTIES
folder menu.
b. Press the (Enter) key to display the log out verification popup
box.
c. Press the ENTER soft key to affirm and log out—or press the ESC soft
key to cancel.
Access Code = ____ ____ ____ ____ ____
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
Enter New Password
0
0 << 65535
60 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 4 Using the HIM
Changing Access Code-protected Drive/Peripheral Parameters
When the host drive is access code-protected, parameter settings for the drive and
its connected peripherals can be viewed—but not changed until after the correct
access code value is entered.
When attempting to edit a parameter value while logged out, the HIM will
prompt you for the access code before allowing access.
Access code protection also applies to:
Drive start-up procedure
Factory defaults
User sets
CopyCat function
Follow these steps to edit access code-protected parameters.
1. Access the Status screen (see Figure 6
).
2. If Port 00 (host drive) is not shown above the ESC soft key, use the
or key to scroll to Port 00.
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the PROPERTIES folder.
5. Use the or key to select Log In.
6. Press the (Enter) key to display the Enter Password popup box.
7. Use the numeric keys to enter the existing access code value.
Use the soft key to delete an erroneous entry.
8. Press the ENTER soft key to enter the existing access code.
Thereafter, any parameter setting can be changed.
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
Enter Password
0
0 << 65535
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 61
Using the HIM Chapter 4
Disabling Access Code Protection
1. Access the Status screen (see Figure 6).
2. If Port 00 (host drive) is not shown above the ESC soft key, use the
or key to scroll to Port 00.
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the PROPERTIES folder.
5. Use the or key to select Log In.
6. Press the (Enter) key to display the Enter Password popup box.
7. Use the numeric keys to enter the existing access code value.
Use the soft key to delete an erroneous entry.
8. Press the ENTER soft key to enter the existing access code.
9. Use the or key to select Change Password.
10. Press the (Enter) key to display the Enter New Password popup box.
11. Use the numeric keys and the soft key to enter ‘0’, the default value to
disable the access code protection feature.
12. Press the ENTER soft key to enter the ‘0’ (disable) default value.
13. After the access code protection verification popup box appears, confirm
the new access code by re-entering ‘0’.
14. Press the ENTER soft key to disable access code protection.
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
Enter Password
0
0 << 65535
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
Enter New Password
0
0 << 65535
62 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 4 Using the HIM
Initiating PowerFlex 750-
Series Drive Port Verification
Upon powerup, the HIM verifies that the PowerFlex 750-Series drive has
initiated Port Verification. The host drive then checks for port conflicts. If any
conflicts are present, a Device Conflicts popup box appears listing all devices with
conflicts.
Conflict Types
If the conflict can be resolved, a ‘!’ symbol precedes the port number. If the
conflict cannot be resolved without removing or replacing the device, an ‘X
symbol precedes the port number. There are five possible conflict types.
In the Device Conflicts popup box, scroll up or down to highlight/select an
individual device row and press the INFO soft key. Another popup box appears
for the selected device showing the type of conflict and related information.
If information is available for the device that previously occupied that port, it will
also be shown.
Use the FIX soft key—displayed only if all conflict types are ‘Changed’ or
‘Requires Configuration’—to resolve conflicts. After pressing the FIX soft key, a
popup box will appear asking to confirm that the new device(s) should be
accepted. Press the ENTER soft key to affirm and resolve the conflicts for all
devices. Thereafter, the HIM will re-read the drive Port Verification information
to make sure that no further conflicts exist.
IMPORTANT
The information in this section does not apply to PowerFlex 7-
Class drives.
Symbol Conflict Type
! Changed
! Requires Configuration
X Not Functioning
X Not Supported
X Invalid Duplicate
IMPORTANT
Please note the following important conflict resolution information:
The Device Conflict popup window remains on the screen until all conflicts
are resolved.
All conflicts must be resolved to access a Folder screen or Control screen.
Only the (Stop) key and the assigned soft keys (INFO and FIX) will be
functional until no conflicts exist.
The host drive will not be able to run while any conflicts are present.
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 63
Using the HIM Chapter 4
Resolving ‘Changed’ or ‘Requires Configuration’ Conflicts
When a ‘Changed’ or ‘Requires Configuration’ conflict exists on powerup, a ‘!’
symbol precedes the port number in the Device Conflicts popup box.
1. Select a port device (in this example, the Encoder card) and press either
the INFO soft key to show additional information about the conflict, or
press the FIX soft key to resolve all device conflicts.
Resolving ‘Not Functioning’, ‘Not Supported’, or ‘Invalid Duplicate’
Conflicts
When a ‘Not Functioning’, ‘Not Supported’, or Invalid Duplicate’ conflict exists
on powerup, an ‘X’ symbol precedes the port number in the Device Conflicts
popup box.
1. Select the port preceded with an ‘X’ (in this example, Port 05) and press
the INFO soft key to show additional information about the conflict (see
example below).
2. Press the ENTER soft key to
affirm and re-display the
Device Conflicts popup box.
Press the ENTER soft key to affirm
and resolve all device conflicts, or
press the ESC soft key to cancel.
Stopped
0.00 Hz
AUTO
Device Conflicts:
! Port 05: I/O Module 24 V
! Port 06: Device Not Found
FIX
F
INFO
! Port 04: Encoder
Stopped
0.00 Hz
AUTO
! 04: Encoder
Changed
Prev: I/O Module 24 V
F
Example screen when the INFO
soft key is pressed.
ENTER
Stopped
0.00 Hz
AUTO
About to permanently
erase the previous
device(s) configuration
Continue?
F
Example screen when the FIX
soft key is pressed.
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
INFO
Device Conflicts:
! Port 04: Encoder
! Port 06: Device Not Found
X Port 05: Not Functioning
64 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 4 Using the HIM
2. Follow the screen prompts to resolve the port conflict.
Or press the ENTER soft key to affirm and re-display the Device Conflicts
popup box.
Changing Language for the
Display Text
All HIM screen text can be displayed in one of the supported languages. The
default language is English.
Follow these steps to select another supported language.
1. Access the Status screen (see Figure 6
).
2. Press the (Language) soft key to display the list of available languages.
3. Use the or key to select the desired language.
4. Press the (Enter) key to enter the selected language.
All HIM screen text now appears in the selected language.
Stopped
0.00 Hz
AUTO
X05: Not Functioning
This device must be
removed or replaced.
Prev: Encoder
F
ENTER
TIP
If the drive is set to a language not supported by the HIM, a popup box appears
asking you to select another language.
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 65
Using the HIM Chapter 4
Updating the HIM Firmware
or Language
Note: The PowerFlex 755T products do not support flashing of DPI options.
This includes the HIMs.
The HIM firmware can be updated over the network or serially through a direct
connection from the drive to the computer using a 1203-USB or 1203-SSS serial
converter.
When updating firmware over the network, you can use the Allen-Bradley
ControlFLASH™ software tool, the built-in update capability of DriveExplorer™
Lite or Full software, or the built-in update capability of DriveExecutive™
software.
When updating firmware through a direct serial connection from the drive to the
computer, you can use the same Allen-Bradley software tools described above, or
you can use HyperTerminal software set to the X-modem protocol.
To obtain a firmware or language update for the HIM, go to http://
www.ab.com/support/abdrives/webupdate. This website contains all firmware
update files, supported language files, and associated Release Notes that describe
the following items:
Firmware update enhancements and anomalies
How to determine the existing firmware revision
How to update the firmware using ControlFLASH, DriveExplorer,
DriveExecutive, or HyperTerminal software
IMPORTANT
When the HIM firmware is updated in the field to support another available
language, the language selected for download will replace all other
supported languages—except English, which always remains as the default
language.
66 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Chapter 4 Using the HIM
Notes:
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 67
Appendix A
Specifications
This appendix provides the specifications for the HIM.
Communications
Electrical
Mechanical
Environmental
Topic Page
Communications
67
Electrical
67
Mechanical
67
Environmental
67
Regulatory Compliance 68
Protocol Drive Peripheral Interface (DPI™)
Data Rates 125 Kbps or 500 Kbps
Consumption 140 mA at 12V DC supplied by the Host Drive
Dimensions
Height
Width
Depth
20-HIM-A6 20-HIM-C6S
116.0 mm (4.57 in.) 180.0 mm (7.08 in.)
70.0 mm (2.75 in.) 93.0 mm (3.66 in.)
16.0 mm (0.63 in.) 25.0 mm (0.98 in.)
Weight 91 g (3.2 oz.) 173 g (5.7 oz.)
Temperature
Operating
Storage
0…50 °C (32…122 °F)
-40…85 °C (-40…185 °F)
Relative Humidity 5…95% noncondensing
Atmosphere Important: The HIM must not be installed in an area where the ambient atmosphere
contains volatile or corrosive gas, vapors or dust. If the HIM is not going to be installed for
a period of time, it must be stored in an area where it will not be exposed to a corrosive
atmosphere.
Vibration
Operating
Non-Operating
2.5 g @ 5 Hz…2 kHz
5 g @ 5 Hz…2 kHz
Shock
Operating
Non-Operating
30 g peak acceleration, 11 (±1) ms pulse width
50 g peak acceleration, 11 (±1) ms pulse width
68 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Appendix A Specifications
Regulatory Compliance
NOTE: This is a product of category C2 according to IEC 61800-3. In a
domestic environment this product may cause radio interference in which case
supplementary mitigation measures may be required.
Certification Specification
UL
c-UL
CE
C-Tick
UL508C
CAN / CSA C22.2 No. 14-M91
EN50178 and EN61800-3
EN61800-3
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 69
Appendix B
HIM Parameters
This appendix provides information about the HIM parameters.
Besides the HIM, the following configuration tools can also be used to monitor
or change parameter values of the HIM, drive, and other connected peripherals:
Connected Components Workbench™ software, version 1.02 or later
DriveExplorer™ software, version 6.01 or later
DriveExecutive™ software, version 5.01 or later
Parameter List
Parameter
No. Name and Description Details
01 [Port Number]
Displays the port on the drive to which the HIM is connected.
Minimum: 1
Maximum: 7
Type: Read Only
02 [DPI™ Data Rate]
Displays the DPI data rate at which the HIM is communicating with
the drive.
Values: 0 = 125 Kbps
1 = 500 Kbps
Type: Read Only
03 [Initial Screen]
Selects the initial HIM screen to be displayed on power up.
Default: 0 = Status Scrn
Value: 0 = Status Scrn
1 = Process Scrn
Type: R ea d/ Write
Reset Required: Yes
04 [Fault Dspy Type]
Selects the type of display flash to be shown when a drive or
peripheral fault is detected.
Default: 1 = Flash Status
Values: 0 = Flash Bklite
1 = Flash Status
2 = Flash None
Type: R ea d/ Write
Reset Required: No
05 [Alarm Dspy Type]
Selects the type of display flash to be shown when a drive alarm is
detected.
Default: 1 = Flash Status
Values: 0 = Flash Bklite
1 = Flash Status
2 = Flash None
Type: R ea d/ Write
Reset Required: No
06 [User Dspy Enable]
Enables/disables the HIM’s automatic user display time function,
which is configured using Parameter 07 - [User Dspy Time].
Default: 1 = Enable
Values: 0 = Disable
1 = Enable
Type: R ea d/ Write
Reset Required: Yes
07 [User Dspy Time]
Sets the amount of time that a screen will remain displayed as long
as the HIM keys are not used. After this time elapses, the screen is
automatically replaced by the initial screen, which is selected
using Parameter 03 - [Initial Screen].
Default: 60 sec
Minimum: 10 sec
Maximum: 300 sec
Type: R ea d/ Write
Reset Required: Yes
70 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Appendix B HIM Parameters
Notes:
Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017 71
Index
A
accessing parameters
alternate linear list method
45
direct parameter access method
44
adjusting display contrast
34
Alarm Dspy Type parameter
69
alarm/fault queues for the drive
46
attentions
12
C
changing PowerFlex 750-Series drive
parameter associations
54
checking drive/peripheral firmware revisions
49
clearing
drive faults/alarms
46
peripheral events
48
compatible products
12
contrast adjustment for display
34
CopyCat function
50
creating user-defined drive/peripheral name
37
customizing the Process screen
38
D
date/time setting for PowerFlex 750-Series
drives
35
diagnostic items for 20-HIM-A6/-C6S HIMs
47
dimensions
67
direct parameter access method
44
disabling password protection
61
display contrast adjustment
34
DPI Data Rate parameter
69
DPI data rates
67
drive fault/alarm queues
46
drive/peripheral firmware revisions - viewing
49
E
events for 20-HIM-A6/-C6S HIMs 49
F
factory defaults 40
Fault Dspy Type parameter
69
fault/alarm queues for the drive
46
features
11
firmware
revision
9
update guidelines
65
H
HIM (Human Interface Module)
adjusting display contrast
34
changing PowerFlex 750-Series drive
parameter associations
54
checking drive/peripheral firmware revisions
49
compatible products
12
CopyCat function 50
creating user-defined drive/peripheral name
37
customizing the Process screen 38
diagnostic items
47
events
49
features 11
firmware or language updating
65
installing
20-HIM-A6 HIM
14
20-HIM-C6S HIM
18
keypad key descriptions
23
LCD display elements/descriptions 26
linking parameters in PowerFlex 700/700S
drives
57
main screens/descriptions 28
parameter list for HIM
69
port verification (only PowerFlex 750-Series
drives)
62
removing
21
resetting the drive/peripherals
40
selecting language for display text 64
setting date/time for PowerFlex 750-Series
drives
35
setting display flashing for
alarm indication
43
fault indication
42
setting factory defaults
40
specifications 67
updating HIM firmware or language
65
using a password
59
viewing peripheral diagnostic items
47
viewing/clearing
drive faults/alarms
46
peripheral events
48
viewing/editing drive and peripheral
parameters
44
I
Initial Screen parameter 69
installing
20-HIM-A6 HIM
14
20-HIM-C6S HIM
18
K
keypad key descriptions 23
L
language
selecting for display text
64
updating
65
72 Rockwell Automation Publication 20HIM-UM001E-EN-P - May 2017
Index
LCD display elements/descriptions 26
linear list access method to parameters
45
linking parameters in PowerFlex 700/700S
drives
57
M
main screens/descriptions 28
manual
conventions
9
related documentation 10
website
10
P
parameters
convention
9
list of
69
password protection
changing parameters
60
disabling 61
setting
59
peripheral diagnostic items - viewing
47
Port Number parameter
69
PowerFlex 750-Series drive port verification
62
products compatible with HIM
12
R
regulatory compliance 68
related documentation
10
removing the HIM
21
resetting the drive/peripherals
40
restoring the drive/peripherals to factory
defaults
40
S
safety precautions 12
screens (main)/descriptions
28
selecting a language
64
setting
display flashing for alarm indication
43
display flashing for fault indication
42
factory defaults
40
password
59
specifications
67
T
technical support 9
time/date setting for PowerFlex 750-Series
drives
35
U
updating HIM firmware or language 65
User Dspy Enable parameter
69
User Dspy Time parameter
69
using the CopyCat function
50
V
verification of ports for PowerFlex 750-Series
drives
62
viewing peripheral diagnostic items
47
viewing/clearing
drive faults/alarms
46
peripheral events 48
viewing/editing drive and peripheral
parameters
44
W
website for related documentation 10
Publication 20HIM-UM001E-EN-P - May 2017
Supersedes Publication 20HIM-UM001D-EN-P - February 2013 Copyright © 2017 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Rockwell Automation Support
Use the following resources to access support information.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the
How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf
.
Technical Support Center
Knowledgebase Articles, How-to Videos, FAQs, Chat, User
Forums, and Product Notification Updates.
https://rockwellautomation.custhelp.com/
Local Technical Support Phone Numbers Locate the phone number for your country. http://www.rockwellautomation.com/global/support/get-support-now.page
Direct Dial Codes
Find the Direct Dial Code for your product. Use the code to
route your call directly to a technical support engineer.
http://www.rockwellautomation.com/global/support/direct-dial.page
Literature Library
Installation Instructions, Manuals, Brochures, and
Technical Data.
http://www.rockwellautomation.com/global/literature-library/overview.page
Product Compatibility and Download
Center (PCDC)
Get help determining how products interact, check
features and capabilities, and find associated firmware.
http://www.rockwellautomation.com/global/support/pcdc.page
.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.
Allen-Bradley, Connected Components Workbench, ControlFLASH, DeviceLogix, DPI, DriveExecutive, DriveExplorer, PowerFlex, Rockwell Automation, Rockwell Software, and SMC are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.