FIGURE 1
AIR HANDLER MOUNTING INSTRUCTIONS:
Attach the adapter collar to the air handler centering
the collar horizontally over the blower opening and
ush with the bottom of the blower. Use #10 x 3/8"
type AB sheet metal screws (eld supplied).
EEH2-0521
45W30-WG1163-01
EEH ELECTRIC
HEATERS
INSTALLATION
MANUAL
GENERAL
The information on the following pages is to provide the
installer the necessary information to properly install the
SpacePak EEH Series electric heaters.
The electric heaters are designed to provide heating
in a heat pump system. The model numbers, kW, and
SpacePak match-ups are shown in the Table 1 below.
See Table 1 and Figure 1 for dimensional information.
LOCATION AND MOUNTING
Before installing the heater, inspect the unit thoroughly for
shipping damage. Check all porcelain insulators for any
breaks and inspect the heater element wire to see that
none have been deformed. Check the heating elements
for loose connections that could cause overheating. If any
shipping damage is found, notify the carrier immediately.
Install the heater by attaching it directly to the air handler
using the adapter collar provided with the heater, as
shown in Figure 2.
Position the unit so the arrow label on the cover of the
electric heater control box is in the direction of the airow.
Shown with Optional Plenum adapter. (45AC-PAJ)
Model EEH-020 EEH-050 EEH-075 EEH-100 EEH-150 EEH-200
Performance
Nominal Output (kw) 2 5 7.5 10 15 20
Nominal Output (BTU's) 6,830 17,076 25,614 34,152 51,228 68,304
Min Airow (CFM)* 100 200 300 500 600 800
Dimensions
L x W x H (inches) Incl Electrical Panel 26 x 19 x 10.5 28 x 19 x 10.5
Shipping (L x W x H inches) 29 x 23 x 13.25 31 x 23 x 13.25
Shipping Weight (lbs) 37 38 46 47
Electrical***
Power Supply (volts/ph/hz) 240/1/60
Control Volts (VDC) 24
Heater Amps (Ckt #1)** 8.3 20 30 40 20 40
Heater Amps (Ckt #2)** N/A 40 40
Min Wire Gauge Dual (AWG) N/A #8 / #6 #6/#6
Min Wire Gauge Single (AWG) #10 #8 #6 #6 #4 #2
Stages 1 2
Air Handler
Applicable
ESP/WCSP 2430 J (H & V)
YES YES YES YES
NO
NO
ESP/WCSP 3642 J (H & V)
YES
ESP/WCSP 4860 J (H & V) YES
*Based upon 70°F entering air and discharge not to exceed 160°F
**@ 240VAC
***To achieve FLA value, air handler amp rating (found on data plate) needs to be added.
TABLE 1: SPECIFICATIONS
W
H
L
2
OPTIONAL ADAPTERS
Table 2 provides a list of optional plenum adapters
available for the electric heater, as shown in Figure 5.
TABLE 2: (OPTIONAL) PLENUM ADAPTERS
Part Number Item Description
45AC-SM9D-PA SmartSeal Plenum Adapter - (J Series)
45AC-PAJ Sheet Metal Plenum Adaptor -(J Seies)
45AC-PAJSQ Fiberboard Plenum Adaptor - (J Series)
FIGURE 5: OPTIONAL ADAPTER
FIGURE 2: HEATER INSTALLATION
Insert the heater into the heater adapter and secure it
using the (4) #8 x ¾ modied Phillips head self drilling
screws shipped with the electric heater.
FIGURE 3
All heaters are suitable for zero clearance between
duct and combustible material. For servicing the control
box, allow enough room to swing the cover open and to
service the blower module, see Figure 4.
FIGURE 4: SERVICE CLEARANCE FOR
HORIZONTAL INSTALLATIONS (TOP VIEW)
The hinge is located on the electric heater control box
closest to the discharge end of the electric heater.
DO NOT HANG UNIT DIRECTLY
FROM HOUSING TO PREVENT DAMAGE TO THE
ELECTRICAL ELEMENTS.
Support the heater on the rafters, oor, or platform with
the air handler. If using a platform, make it large enough
to support the entire heater and air handler.
ELECTRIC HEATER
ELECTRIC HEATER ADAPTER
(SUPPLIED WITH ELECTRIC HEATER)
HORIZONTAL AIR HANDLER
(FASTENERS SUPPLIED WITH
ELECTRIC HEATER)
ELECTRIC HEATER ADAPTER GASKET
(SUPPLIED WITH ELECTRIC HEATER)
SPL-WG1085_A
1 3/4 +/- 1/8
SPL-WG1093_A
ELECTRIC HEATER
HORIZONTAL AIR HANDLER
ELECTRIC HEATER MUST BE SUPPORTED
TO PREVENT EXCESSIVE STRESS
ON THE AIR HANDLER
24.00
ELECTRIC HEATER
HORIZONTAL AIR HANDLER
MAIN PLENUM
AIRFLOW
SPL-WG1087_A
PLENUM ADAPTER
45AC-PAJ
ELECTRIC HEATER
SPL-WG1091_A
FASTENERS SUPPLIED BY FIELD
PLENUM ADAPTER
45AC-PAJSQ
ELECTRIC HEATER
SPL-WG1092_A
FASTENERS SUPPLIED BY FIELD
PLENUM ADAPTER
45AC-SM9D-PA
ELECTRIC HEATER
SPL-WG1090_A
FASTENERS SUPPLIED BY FIELD
3
INSULATION
SPL-WG1089_A
For both vertical and horizontal installations always
allow a minimum of 18 inches (457 mm) of straight duct
between the discharge side of the electric heater and
any tee or elbow as shown in Figure 6.
FIGURE 6: LOCATION (TOP VIEW)
Note: All metal connections must be mechanically
fastened with sheet metal screws and the joints and
seams must be taped with UL- 181A-P foil faced tape or
or sealed with UL-181A-M duct mastic.
INSULATION
Insulate all metal ducting with 1.5-inch (38-mm) minimum
berglass insulation. For round duct, use either sleeve
insulation or foil-faced duct wrap. For square duct use
either berglass duct board or foil-faced duct wrap. Tape
all seams to prevent air leaks.
When the heater is installed in high humidity areas,
such as an unconditioned attic or crawlspace, there is a
possibility of condensation forming on the heater cabinet
during the cooling mode. To prevent condensation, cover
the heater with 1-inch (25-mm) foil faced berglass
insulation or duct board including the underside between
the heater and support platform. Be sure to allow access
to the control box cover for servicing. See Figure 7.
Insulate exterior cabinet, except the control panel, with a
minimum of 1.0" [25mm] thick berglass or foam rubber.
FIGURE 7
WIRING
DISCONNECT ELECTRICAL SUPPLY
BEFORE WIRING UNIT TO PREVENT INJURY OR
DEATH FROM ELECTRICAL SHOCK.
All electrical wiring must comply with all local codes and
ordinances. Use the 15 amp breaker integrated into the
heater for the air handler power supply.
Open the heater cover and connect the power supply to
terminals L1 and L2 on the high voltage terminal block.
See appropriate wiring diagram (Figures 9-14) to select
the correct wire gauge for the specic amperage of
the heater being installed. Connect a ground wire
to the ground lug labeled G. Terminals M1 and M2
on the heaters are for output power to the blower. 15
and 20kw heaters there are two breakers so you can
wire one (single) or two (dual) line input circuits. Refer
to appropriate wiring diagram (Figures 9-14) and the
label on the control box lid for specic wire sizes and
amperage.
Connect the 24V control wiring as shown in the appropriate
wiring diagram.
It is important to use a thermostat designed for use with
electric heat or two-stage heating. The internal wiring
diagrams are shown in Figures 9 through 14. The 15
and 20 kW single phase heaters contain two supply
circuits. Supply wires can be run separately for each
circuit, which is the default conguration. Using two
supply circuits allows the use of smaller gauge wires. In
some cases, it is necessary to use smaller gauge wire to
comply with building codes that limit the maximum wire
size that can be used for a single circuit.
18.00
SPL-WG1088_A
ELECTRIC HEATER
HORIZONTAL AIR HANDLER
T
EE OR ELBOW
MAIN PLENUM
4
FIGURE 8: JUMPER BAR SHOWN INSTALLED ON
CIRCUIT BREAKERS.
Note: Circuit breakers installed in this device are the
short-circuit protection of internal wiring and to serve as
a service disconnect. Circuit breakers installed within
this device DO NOT provide over current protection of
the supply wiring.
SEQUENCE OF OPERATION
All heaters have a built-in delay feature to delay the
heater from coming on before the air handler is operating.
There is no delay-off feature. As soon as the thermostat
is satised, the heater de-energizes and the air handler
will continue running for approximately 1 minute. An air
pressure switch is in series with the fan interlock relay for
added protection and safety. The heater is designed for
a softer start so that there is a short time delay between
stages.
CAPACITY AT LOWER VOLTAGES
The elements are rated at 240 Volts and should not be
used at higher voltages. Lower voltages are acceptable.
However, heaters are resistive loads so capacity is
reduced by the square of the voltage ratio.
kW (output) = kW (rated) x (V/240)
2
Therefore, multiply the rated capacity by the factor
shown in Table 3 to determine the actual output of the
heater at other voltages.
TABLE 3: HEATER CAPACITY FACTOR
AT OTHER VOLTAGES
Voltage Factor
240 1.00
230 0.92
220 0.84
DUCT DESIGN
The design of the duct system must account for the added
restriction of the heater. Table 4 lists the static pressure
drop of the heaters. Usually it will be necessary to add
additional outlets to account for the added restriction,
particularly for the systems requiring more than 800
CFM (378 L/s). For these systems it is not unusual to
have 7 outlets per ton.
TABLE 4: PRESSURE DROP, INCHES OF WATER (PA)
External Electric Heater Models
CFM (m
3
/min) 2 Kw 5 kW 7.5 kW 10 kW 15 kW 20 kW
100(2.83) 0(0.64) 0(0.64) 0(0.8) 0(0.8) 0.01(1.28) 0.01(1.28)
125(3.54) 0(1.0) 0(1) 0.01(1.25) 0.01(1.25) 0.01(2.01) 0.01(2.01)
150(4.25) 0.01(1.44) 0.01(1.44) 0.01(1.79) 0.01(1.79) 0.01(2.89) 0.01(2.89)
175(4.96) 0.01(1.96) 0.01(1.96) 0.01(2.44) 0.01(2.44) 0.02(3.93) 0.02(3.93)
200(5.66) 0.01(2.55) 0.01(2.55) 0.01(3.19) 0.01(3.19) 0.02(5.14) 0.02(5.14)
250(7.08) 0.02(3.99) 0.02(3.99) 0.02(4.98) 0.02(4.98) 0.03(8.02) 0.03(8.02)
300(8.50) 0.02(5.75) 0.02(5.75) 0.03(7.17) 0.03(7.17) 0.05(11.56) 0.05(11.56)
350(9.91) 0.03(7.82) 0.03(7.82) 0.04(9.76) 0.04(9.76) 0.06(15.73) 0.06(15.73)
400(11.33) 0.04(10.22) 0.04(10.22) 0.05(12.75) 0.05(12.75) 0.08(20.54) 0.08(20.54)
450(12.74) 0.05(12.93) 0.05(12.93) 0.06(16.14) 0.06(16.14) 0.1(26) 0.1(26)
500(14.16) 0.06(15.97) 0.06(15.97) 0.08(19.92) 0.08(19.92) 0.13(32.1) 0.13(32.1)
550(15.57) 0.08(19.32) 0.08(19.32) 0.10(24.1) 0.10(24.10) 0.16(38.84) 0.16(38.84)
600(16.99) 0.09(22.99) 0.09(22.99) 0.12(28.68) 0.12(28.68) 0.19(46.22) 0.19(46.22)
650(18.41) 0.11(26.98) 0.11(26.98) 0.14(33.66) 0.14(33.66) 0.22(54.25) 0.22(54.25)
700(19.82) 0.13(31.29) 0.13(31.29) 0.16(39.04) 0.16(39.04) 0.25(62.91) 0.25(62.91)
750(21.24) 0.14(35.92) 0.14(35.92) 0.18(44.82) 0.18(44.82) 0.29(72.22) 0.29(72.22)
800(22.65) 0.16(40.87) 0.16(40.87) 0.20(51.00) 0.20(51.00) 0.33(82.17) 0.33(82.17)
850(24.07) 0.19(46.14) 0.19(46.14) 0.23(57.57) 0.23(57.57) 0.37(92.76) 0.37(92.76)
900(25.49) 0.21(51.73) 0.21(51.73) 0.26(64.54) 0.26(64.54) 0.42(104.00) 0.42(104.00)
950(26.90) 0.23(57.64) 0.23(57.64) 0.29(71.91) 0.29(71.91) 0.47(115.87) 0.47(115.87)
1000(28.32) 0.26(63.87) 0.26(63.87) 0.32(79.68) 0.32(79.68) 0.52(128.39) 0.52(128.39)
1050(29.73) 0.28(70.41) 0.28(70.41) 0.35(87.85) 0.35(87.85) 0.57(141.55) 0.57(141.55)
1100(31.15) 0.31(77.28) 0.31(77.28) 0.39(96.41) 0.39(96.41) 0.62(155.35) 0.62(155.35)
1150(32.56) 0.34(84.46) 0.34(84.46) 0.42(105.38) 0.42(105.38) 0.68(169.80) 0.68(169.80)
1200(33.98) 0.37(91.97) 0.37(91.97) 0.46(114.74) 0.46(114.74) 0.74(184.88) 0.74(184.88)
1250(35.40) 0.40(99.79) 0.40(99.79) 0.50(124.5) 0.5(124.50) 0.81(200.61) 0.81(200.61)
PRESURE DROP, INCHES WC (Pa)
5
FIGURE 9: MODEL EEH-020 WIRING DIAGRAM
MODEL #EEH-020
KILOWATTS
2.0
VOLTS/PH/Hz 240/1/60
CONTROL VOLTS 24
STEPS 1
HEATER AMPS 8.3
CIRCUIT BREAKER 1/2 15 / 15
V.A. (CONTACTOR RELAYS)
15
F.P.M. (AIR VELOCITY)
350
MIN. WIRE GA. CU # 10 AWG
6
FIGURE 10: MODEL EEH-050 WIRING DIAGRAM
MODEL #EEH-050
KILOWATTS
4.8
VOLTS/PH/Hz 240/1/60
CONTROL VOLTS 24
STEPS 1
HEATER AMPS20
CIRCUIT BREAKER 1/2 15 / 25
V.A. (CONTACTOR RELAYS)
15
F.P.M. (AIR VELOCITY)
560
MIN. WIRE GA. CU # 8 AWG
7
FIGURE 11: MODEL EEH-075 WIRING DIAGRAM
MODEL #EEH-075
KILOWATTS 7.2
VOLTS/PH/Hz 240/1/60
CONTROL VOLTS 24
STEPS 1
HEATER AMPS30
CIRCUIT BREAKER 1/2 15 / 40
V.A. (CONTACTOR RELAYS)
17
F.P.M. (AIR VELOCITY)
750
MIN. WIRE GA. CU # 6 AWG
8
FIGURE 12: MODEL EEH-100 WIRING DIAGRAM
MODEL #EEH-100
KILOWATTS
9.6
VOLTS/PH/Hz 240/1/60
CONTROL VOLTS 24
STEPS 1
HEATER AMPS40
CIRCUIT BREAKER 1/2 15 / 50
V.A. (CONTACTOR RELAYS)
17
F.P.M. (AIR VELOCITY)
1150
MIN. WIRE GA. CU # 6 AWG
9
FIGURE 13: MODEL EEH-150 WIRING DIAGRAM
MODEL #EEH-150
KILOWATTS 14.4
VOLTS/PH/Hz 240/1/60
CONTROL VOLTS 24
STEPS 2
HEATER AMPS 20.0 / 40.0
CIRCUIT BREAKER 1/2/3
15 / 25 / 50
V.A. (CONTACTOR RELAYS)
26
F.P.M. (AIR VELOCITY)
1150
MIN. WIRE GA. CU, DUAL (JMPR / CB3)
# 8 / # 6 AWG
MIN. WIRE GA. CU, SINGLE
# 4 AWG
10
FIGURE 14: MODEL EEH-200 WIRING DIAGRAM
MODEL #EEH-200
KILOWATTS
19.20
VOLTS/PH/Hz 240/1/60
CONTROL VOLTS 24
STEPS 2
HEATER AMPS 40.0 / 40.0
CIRCUIT BREAKER 1/2/3
15 / 50 /50
V.A. (CONTACTOR RELAYS)
26
F.P.M. (AIR VELOCITY)
1150
MIN. WIRE GA. CU, DUAL (JMPR / CB3)
# 6 / # 6 AWG
MIN. WIRE GA. CU, SINGLE
# 2 AWG
11
TABLE 5: REPLACEMENT PARTS LIST
Quantity Per Unit
Item SP Part No. EEH-020 EEH-050 EEH-075 EEH-100 EEH-150 EEH-200
Limit Switch, 133F 45W41-WG1098-01 1 1 1 1 1 1
Circuit Breaker, 2 POLE, 50A 45W41-WG1099-01 0 0 0 1 1 2
Circuit Breaker, 2 POLE, 40A 45W41-WG1167-01 0 0 1 0 0 0
Circuit Breaker, 2 POLE, 25A 45W41-WG1100-01 0 1 0 0 1 0
Circuit Breaker, 2 POLE, 15A 45W41-WG1101-01 2 1 1 1 1 1
Contactor, 2 pole, 40A 45W41-WG1102-01 1 1 1 2 2 4
Ground Lug, #6-#14 awg 45W41-WG1103-01 1 1 1 1 1 1
Ground Lug, 1/0-#14 awg 45W41-WG1104-01 0 0 0 1 1 1
Jumper Bar, 4-Pole 45W41-WG1105-01 1 1 1 1 1 1
Latch 45W41-WG1106-01 1 1 1 1 1 1
Thermal cutoff switch, 158C 45W41-WG1107-01 1 1 2 2 3 4
Element rack, 2 kW 45W41-WG1168-01 1 0 0 0 0 0
Element rack, 5 kW 45W41-WG1169-01 0 1 0 0 0 0
Element rack, 7.5 kW 45W41-WG1170-01 0 0 1 0 0 0
Element rack, 10 kW 45W41-WG1108-01 0 0 0 1 0 0
Element rack, 15 kW 45W41-WG1109-01 0 0 0 0 1 0
Element rack, 20 kW 45W41-WG1110-01 0 0 0 0 0 1
Rectier with 5 sec delay 45W41-WG1111-01 1 0 1 1 1 1
Rectier with 9 sec delay 45W41-WG1112-01 0 1 1 1 1 1
Rectier with 18 sec delay 45W41-WG1113-01 0 0 0 0 1 1
Terminal block, 3 pole 45W41-WG1114-01 1 1 1 1 1 1
Switch, diff P, .05" WC 45W41-WG1115-01 1 1 1 1 1 1
Timer, delay on make 45W41-WG1116-01 0 0 0 0 1 1
Lamp, indicator, red 45W41-WG1117-01 1 1 1 1 2 2